Interval Function - Viessmann VITOSOLIC 200 Installation And Service Instructions Manual

Electronic temperature differential control unit
Table of Contents

Advertisement

Interval function

■ Activation of this function in systems
with unfavourably located collector
temperature sensor. Consequently
delays in capturing the collector tem-
perature are prevented.
■ The solar circuit pump can be switched
ON for a set period in a freely selecta-
ble interval.
Delivered condition:
The solar circuit pump is switched ON
from 07:00 ("Int ON") to 19.00 ("Int
OFF") h every 30 min ("Interval") for
30 s ("Int time").
This function is disabled from 19:00 to
07:00 h.
Note
This function will be suppressed if the
collector temperature sensor is faulty or
the collector shutdown temperature
"Tcolemoff" has been reached (see
page 154).
Make the following settings at the
solar control unit:
1. Main menu
■ "Solar"
■ "Options"
– "Col.interv."
Set "Yes".
Function description
2. Main menu
■ "Solar"
■ "Contractor"
– "Int time"
Set the runtime for the solar cir-
cuit pump in the selected inter-
val.
– "Int ON"
Set the time when the function
should start.
– "Int OFF"
Set the time when the function
should stop.
3. Main menu
■ "Solar"
■ "Setting values"
– "Interval"
Interval between starting and
stopping the solar circuit pump.
127