Minimum collector temperature limit
Minimum start temperature "TColmin"
that must be exceeded before the solar
circuit pump can start. This prevents the
pump starting too frequently. The collec-
tor array will be blocked if this tempera-
ture is not achieved.
Cyclical heating
■ If the consumer cannot be heated with
priority, the next consumer in line will
be heated for an adjustable cycle time
"t-circ.".
■ After this time has expired, the solar
control unit checks the rise of the col-
lector temperature during the cyclical
pause time "t-stop".
If the value "ΔT Col" is reached, "t-
stop" is set to zero and starts again.
■ As soon as the start conditions for the
consumer with priority have been met,
that consumer will be heated again.
Otherwise, the next-in-line consumers
will continue to be heated.
■ Once the consumer with priority has
reached its set temperature "Tcyl
set", it will no longer be taken into con-
sideration for cyclical heating.
Function description
Make the following settings at the
solar control unit:
Main menu
■ "Solar"
■ "Contractor"
– "TColmin"
Set a value.
Make the following settings at the
solar control unit:
Main menu
■ "Solar"
■ "Contractor"
– "t-stop"
Set a value.
– "t-circ."
Set a value.
– "ΔT Col"
Set a value.
When the consumers have reached their
set value "Tcyl set", heating to a higher
value "Tcyl2 set" can continue. This
function can be activated separately for
each consumer.
Make the following settings at the
solar control unit:
1. Main menu
■ "Solar"
■ "Contractor"
– "Cyl set"
Select the consumer that this
function should affect.
Set "Yes".
135