Specifications; Ordering Information - Gemini GEM-P9600 Installation Instructions Manual

Control panel/communicator
Hide thumbs Also See for Gemini GEM-P9600:
Table of Contents

Advertisement

WI742E 2/04

SPECIFICATIONS

GEM-P9600
Panel Dimensions: 12 3/8" x 13 7/8" x 3 ½" (H x W x D) without cover
Operating Temperature: 0-49°C (32-120°F)
Input Power: 16.5VAC via CLASS 2 Plug-In 40VA or 50VA Transformer
Loop Voltage: 10-13VDC
Loop Current: 2.4mA with 2.2K Ohm end-of-line resistor (Model EOL2.2K); 5mA for 2-wire smoke-detector zones; 1.4
mA using a 3.9K Ohm resistor (Model EOL 3.9K) with Zone Doubling
Loop Resistance: 300 Ohm max.; 50 Ohm for 2-wire smoke-detector zones
Relay Outputs (Burglary; Reset; Aux): Wet, 12Vdc, 1.2A max.; Dry (cut related jumper for dry contacts; see Wiring Dia-
gram), SPDT contacts 24Vdc, 2A, 0.6 PF
Auxiliary Power Output: 12Vdc regulated
Remote Power Output: 12Vdc regulated (for keypads)
Combined Standby Current (Remote Power + Aux. Power + Reset Relay Power): See following charts.
TRANSFORMER
TRF11 (16.5 VAC, 40 VA)
TRF11 (16.5 VAC, 40 VA)
TRF11 (16.5 VAC, 40 VA)
TRF11 (16.5 VAC, 40 VA)
TRANSFORMER
TRF11 (16.5 VAC, 40 VA)
(1)
Note:
With 1 RBAT6 battery, GEM-P9600 combined standby current + PS3002 standby current may not exceed 1.2A.
(2)
W(2) With 2 RBAT6 batteries, GEM-P9600 combined standby current + alarm current may not exceed 1.9A.
Standby Time: Residential Fire/Burglary & Commercial Burglary, 24 hours minimum
EZM Module: GEM-EZM8: Input, 50mA (not including PGM output)
PGM Output: 5mA, 12V Special Application
Keypad Current:
GEM-RP1CAe2/GEM-K1CA: 100mA; 35mA if backlighting is disabled (cut W1, W2 & W3)
GEM-RP2ASe2/GEM-K2AS: 50 mA
GEM-RP3DGTL/GEM-K3DGTL: 50 mA
GEM-RP4RFC/GEM-K4RF: 75mA Standby
GEM-RP4C/GEM-K4: 45mA Standby
PGM Output: 5mA, 12V Special Application
Maximum Number of Keypads: 15
Maximum Wiring Length for each run (#22AWG): 1000' divided by total number of keypads and EZMs on run
Keypad Dimensions: 4 ¼" x 5 ¾" x 1" (H x W x D); 11.1cm

ORDERING INFORMATION

System Components
GEM-P9600: Residential UL-Listed Burg Control Panel.
GEM-RP1CAe2/GEM-K1CA: 32-Character LCD Burg & Residential Fire Keypad with 4 EOL resistor supervised Zones.
GEM-RP2ASe2/GEM-K2AS: LCD Burg & Residential Fire Keypad with remote panic.
GEM-RP3DGTL/GEM-K3DGTL: Digital Burg and Residential Fire Keypad with remote panic.
GEM-RP4RFC/GEM-K4RF: Digital Icon Burg and Residential Fire Keypad with Integral RF Receiver.
GEM-RP4C/GEM-K4: Digital Icon Burg and Residential Fire Keypad.
L
NAPCO Security Systems
RESIDENTIAL BURGLARY & COMMERCIAL BURGLARY
RECHARGEABLE
BATTERY
RBAT4 (12 VDC, 4 AH)
RBAT6 (12 VDC, 6 AH)
(3)
RBAT6 (12 VDC, 6 AH)
PS3002 (13.2 VDC, 1.9 A)
(3)
2 RBAT6 (12 VDC, 6 AH)
PS3002 (13.2 VDC, 1.9 A)
RESIDENTIAL FIRE, COMBINATION RESIDENTIAL FIRE & BURGLARY
RECHARGEABLE
BATTERY
RBAT7 (12 VDC, 7 AH)
POWER
GEM-P9600 COM-
BINED
SUPPLY
STANDBY CURRENT
N/A
750 mA
N/A
750 mA
750 mA
750 mA
GEM-P9600
COMBINED
STANDBY CURRENT
150 mA
X
GEM-P9600
POWER SUPPLY
ALARM
STANDBY
CURRENT
CURRENT
2.0 A
N/A
2.0 A
N/A
(1)
(2)
1.9 A
1.2 A
1.9 A
1.4 A
GEM-P9600
STANDBY
ALARM
TIME
CURRENT
650 mA
24 Hours
GEM-P9600 Installation Instructions
!
Page 7
STANDBY
TIME
4 Hours
6 Hours
(1,2)
4 Hours
4 Hours

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gem-p9600

Table of Contents