G E M - P 9 6 0 0 CONTROL PANEL/COMMUNICATOR For use with "Classic" keypads (GEM-RP1CAe2, GEM-RP2ASe2, GEM-RP3DGTL and GEM-RP4RFC/GEM-RP4C) and with "K Series" keypads (GEM-K1CA, GEM-K2AS, GEM-K3DGTL, and GEM-K4RF/GEM-K4) G E M I N I SYSTEM READY GEMINI SYSTEM ARMED 01/01/03 12:00 AM READY 01/01/97...
THIS MANUAL INCLUDES FEATURES WHICH ARE ONLY AVAILABLE IN CONTROL PANEL FIRM- WARE VERSION 20 OR LATER. CHANGES FROM PREVIOUS EDITION The following changes have been made to this manual (WI742D) since the last edition (WI742C). Changes to the following existing Glossary entries: Abort Delay Access Control;...
Page 3 IMPORTANT NOTE This manual supports the keypad programming of the GEM-P9600 control panel with the NAPCO "classic" GEM- RP1CAe2, GEM-RP2ASe2, GEM-RP3DGTL and GEM-RP4RFC/GEM-RP4C keypads as well as the GEM-K1CA, GEM- K2AS, GEM-K3DGTL, and GEM-K4RF/K4 "K Series" keypads. The new "K Series" models offer the new STAY and AWAY buttons with simplified functionality, along with the new MENU and ENTER buttons.
Basic Zone Configuration ........16 Expanded Zone Configuration ......16 Refer to accompanying GEM-P9600 Programming Instructions (WI777 and WI1185) for programming information. NOTE: THESE INSTRUCTIONS ARE INTENDED AND WRITTEN FOR PROFESSIONAL INSTALLATION PERSONNEL HAVING SUITABLE TRAINING, EXPERIENCE AND INSTALLATION EQUIPMENT. IT IS RECOMMENDED THAT AFTER PROGRAMMING, THE ERROR CHECK UTILITY OF THE PCD3000 (OR PCD-WINDOWS) DOWNLOADER SOFTWARE BE USED TO VERIFY THAT THE CONTROL PANEL PRO- GRAM CONTAINS NO ERRORS OR CONFLICTS WHICH MAY INHIBIT ITS INTENDED OPERATION.
GEM-P9600M The standard GEM-P9600 may be converted to the Mercantile “GEM-P9600M” version with the optional accessory, H1217. The H1217 kit includes the model H217 heavy-duty UL commercial enclosure, the required (2) tamper switches and required tamper screws. Note: Do not use Fire Zones in a Mercantile installation.
Access only capability. Provisions for fire, police and auxiliary panic alarms. Integral 4-zone EZM included in each keypad (GEM-RP1CAe2/GEM-K1CA only). Communicator Test to Central facilitates testing; Locate, Fault-Find and EZM-Locate diagnostics simplify trouble- shooting. PGM output. NAPCO Security Systems GEM-P9600 Installation Instructions...
24 Hours Note: With 1 RBAT6 battery, GEM-P9600 combined standby current + PS3002 standby current may not exceed 1.2A. W(2) With 2 RBAT6 batteries, GEM-P9600 combined standby current + alarm current may not exceed 1.9A. Standby Time: Residential Fire/Burglary & Commercial Burglary,...
Do not program any zones for “Keyswitch Arming” System must be serviced at least once every year Residential Fire and Combination Residential Fire & Burglary must program “Residential Fire” Keypad Expansion (EZM) Zones are not to be used as fire zones NAPCO Security Systems GEM-P9600 Installation Instructions...
Then, using hardware suitable for the mounting surface, add one or two screws at the right side of the keypad case directly into the wall to ensure a secure installation. Note: Do not overtighten the screws! Uneven walls may cause the keypad case to distort. NAPCO Security Systems GEM-P9600 Installation Instructions...
CAUTION: Do not run telephone wiring near speaker wires; do not run keypad wiring with loop wiring. Adding Expansion Zones GEM-P9600 Series control panels will handle up to 8 zones as is, however this number may be increased to as many as 96 programmable zones using optional expansion zone modules (EZMs).
In addition to Grade-B Requirements (above), one relay on the RM3008 must be programmed to trip the Ademco 7720 when the telephone line fails. Daily openings and closings are required to be transmitted by the Napco panel along with the 24-hour DACT test signal and DACT trouble conditions. NAPCO Security Systems GEM-P9600 Installation Instructions...
The last received signal strength for each transmission is always stored in memory and can viewed at any time using this procedure. Signal strength can also be viewed through the PCD3000 Status Screen. NAPCO Security Systems GEM-P9600 Installation Instructions...
P9600 Programming Instructions). Connect the device controlled by the programmable output between terminal 8 (+) and terminal 14 (-). A programming option “Aux. Output Chirp on Key- fob Arming” is available. If selected, an external siren driver can be connected to these termi- nals. NAPCO Security Systems GEM-P9600 Installation Instructions...
Auxiliary Power provides a filtered 12 VDC nominal output which is used for powering auxiliary AUX POWER devices. NOTE: To calculate the available standby time refer to the Standby-Battery Calculation Worksheet at the back of this manual. NAPCO Security Systems GEM-P9600 Installation Instructions...
(2 LINE LCD KEYPAD) The GEM-P9600 Control Panel may be expanded up to 96 zones. This may be accomplished by adding 88 zones to the basic 8 zone configuration. Hardwired zone expanders include: GEM-EZM4 (4 additonal zones per module), GEM- EZM8 (8 additional zones per module) and GEM-RP1CAe2 Keypad (4 additional zones per keypad).
4-WIRE SMOKE DETECTOR WIRING ( - ) The GEM-P9600 can use conventional 12 VDC 4-wire smoke detectors. To use them, the select fire zone programming option and do not select 2-wire smoke detector pro- gramming option for the desired fire zone (refer to the GEM-P9600 Programming In- structions).
This line should not be connected to party lines or coin operated telephones. If connected to a line with call waiting, then call waiting interrupt numbers must be programmed into the CS Telephone Numbers (refer to the GEM-P9600 Programming Instructions).
A valid number will be acknowledged by a short beep; an invalid number will be rejected by a long beep. 2. Press the button to continue or press the button to exit. NAPCO Security Systems GEM-P9600 Installation Instructions...
Page 20
Keypad Configuration Mode (No Message) **Enter Now** 01 OUT OF SYSTEM (display will read “ ”). Then replace Jumper JP5 across Pins 1–2 Door Control (top two). Gate Control Light Control Control #1 Control #2 NAPCO Security Systems GEM-P9600 Installation Instructions...
Page 21
Cut Jumper C to disable the sounder. (Do not disable in UL applications.) NAPCO Security Systems, Inc. 333 Bayview Avenue, Amityville, New York 11701 For Sales and Repairs, call toll free: (800) 645-9445 For direct line to Technical Service, call toll free: (800) 645-9440 Internet: http://www.napcosecurity.com NAPCO Security Systems GEM-P9600 Installation Instructions...
USER CODES & ZONE DESCRIPTIONS (Refer to the GEM-P9600 Programming Instructions (WI777 and WI1185) for a detailed explanation of programming). Up to 96 personal user codes may be programmed at the keypad. NOTE: The Area Options associated with each User Code may only be programmed in the Dealer Program Mode.
"000" in intervals of 10 seconds, indicating the avail- able time remaining to disarm the panel. (Note: The sounder will "pulse" with the GEM-P9600/3200 version 30 and above, and with the GEM-P1632/816 version 10 and above.
Manager's Mode, is a low-security mode of operation. It provides quick access to other areas without having to go to another keypad of another area. To arm or disarm the alternate area (for "Classic" keypads): 1. Press a button between representing the alternate area. 2. Press the button, then the button. NAPCO Security Systems GEM-P9600 Installation Instructions...
The alarm con- ditions will then be stored in the Alarm History Log and the Total Event Log (see HISTORY LOG). NAPCO Security Systems GEM-P9600 Installation Instructions...
DISPLAY FIRE TRBL To display Fire Zone(s) in trouble, access DISPLAY FIRE TRBL and scroll through the zones using the NEXT button. Cor- rect the problem, then press the button to restore the "SYSTEM READY" condition. NAPCO Security Systems GEM-P9600 Installation Instructions...
Page 27
If the central station ringback signal has not been received within about 30 seconds, a communication problem may exist. Press YES button to start exit delay manually. FAULT FIND This troubleshooting aid will help the installer locate swingers. When accessed, two things occur: NAPCO Security Systems GEM-P9600 Installation Instructions...
Page 28
Within this countdown window, arming may be delayed an additional 1 to 4 hours, as above, or autoarming may be canceled by arming and disarming the panel. NAPCO Security Systems GEM-P9600 Installation Instructions...
Note: A signal strength of 3 or less is an indication that reception may be unreliable. In such cases, the use of an additional receiver located closer to the transmitter is recommended. If two receivers are connected to the GEM-P9600, only the higher signal strength of the two will be displayed. RELAY CONTROL Press the YES button to check the status (all on or all off) of up to 8 groups programmed with any combination of up to 96 available external relays.
Access Control; Access Control (Panel Access) on Aux Output; Aux Output Access Control Time; Panel Access NOTE: The GEM-P9600 has not been evaluated by UL for compliance with UL294 (Access Control Systems). The Aux Output can be programmed to activate for a programmable period of time (2 to 254 sec.). This allows it to be used for ac- cess functions such as opening and closing a garage door, or remotely activating an electric door strike through an RB1000 relay.
Page 32
Alarm on Day Zone See Day Zone Alarm Outputs (See Wiring Diagram for UL requirements.) The GEM-P9600 has three Form-C relay outputs: Burglary, Auxiliary and Reset. Each has a related jumper (B, A, and C, respectively) that may be cut for dry contacts.
Page 33
Output Timeout and Auto-Reset. Zones that are not programmed for Auto-Reset will not be capable of signaling another alarm until (a) the cause of the alarm has been corrected and (b) the control panel is disarmed. Also see Swinger Shutdown. Auxiliary Relay See Alarm Outputs Backup Report on Telco 2 NAPCO Security Systems GEM-P9600 Installation Instructions...
Page 34
ACTIVATE CHIME function to enable or disable the Chime Mode from the keypad. This feature is programmable by zone and for duration of tone (see Time Selection). A time (in ¼ seconds) must be programmed for the chime to function. NAPCO Security Systems GEM-P9600 Installation Instructions...
Page 35
This format should be preferred whenever the central station is capable of receiving it. After transmitting the Subscriber Identification Number and the Alarm Code, the communicator sends a verifying digit that is the sum of both. NAPCO Security Systems GEM-P9600 Installation Instructions...
Page 36
Pager (Telco 3) Report Delay Programmable delay of the Telco 3 report (typically used for Pager Reporting) intended to allow time for central station to to allow to verify alarm report the alarm report. Compatible Receivers. The following receivers are compatible with the GEM-P9600. •...
Page 37
• If 24-hour zone is open at end of test, no report is sent (GEM-P9600). If a 24-hour zone is tripped and not restored during Fault Find, when the mode is exited the zone will display as "Faulted" on the keypad display.
Page 38
SIA CP-01 standards: (1) Exit Delay Time: If an at- tempt is made to change the Exit Delay time to less than 45 seconds the time will be entered as 60 seconds. The maximum pro- NAPCO Security Systems GEM-P9600 Installation Instructions...
Page 39
The default setting for this option is enabled. Restart events are logged. (SIA CP-01: 4.2.2.3). Exit Urgency Annunciation When armed Away, exit is audible, and time is 60 seconds (default). Enabled with "Enable CP-01 Limits" in the EZ Program Menu. NAPCO Security Systems GEM-P9600 Installation Instructions...
Page 40
” reminder will go out upon arming, denoting full protection, however Interior (Stay) Zones will once again be bypassed the next time the panel is disarmed. If “Auto Interior Bypass” is programmed, all Interior Zones will automatically be bypassed if the Exit/Entry doors are not opened during NAPCO Security Systems GEM-P9600 Installation Instructions...
Page 41
Keyfobs can be assigned to zones to allow individual reporting. Each of the 4 keyfob buttons can be assigned to a zone. For example, On button = point 1; Off button = point 2; A1 = point 3; A2 = point 4. Up to 96 keyfobs can be assigned to the GEM-P9600, providing multiple wireless panic buttons on a system, each reporting to the Central Station or a pager and/or annunciating on a key- pad the keyfob zone number with description/location.
Page 42
When a fire zone is bypassed the panel will go into a fire trouble condition. It will also transmit the fire trouble to the CS, if programmed to do so. Zones 1-9 are entered as 01 - 09. Loop Response (750mS required for UL installations) NAPCO Security Systems GEM-P9600 Installation Instructions...
Page 43
Report Code. Modem IIe CS Format The GEM-P9600 control supports Radionics Modem IIe central station reporting format. Never Arm (Do not use for primary Burglary protection) A zone programmed as Never Arm cannot go into alarm. If tripped, it will display at the keypad when the DISPLAY STATUS function is selected.
Page 44
Page 44 WI742D 5/03 Opening/Closing Reporting for Key-fob Users Key-Fob users can now report openings and closings. • GEM-P9600: Key Fobs 1-16 report as Users 81-96. Panics Keypad Aux Panic Keypad (Police) Panic Keypad Fire Panic See Fire Remote Panic The Panic Zone is always a 24-Hour Zone.
Page 45
Resound on Wireless Smoke Low Battery If a wireless smoke detector low battery is detected, it will re-sound the trouble at the keypad every 4 hours when disarmed and every 12 hours when armed, until the condition is corrected. NAPCO Security Systems GEM-P9600 Installation Instructions...
Page 46
Install a 130Ω resistor across the 2 terminals of each zone used (color code: brown/orange/brown). Wire positive (+) terminal of smoke detector to terminal 28. Wire negative (-) terminal of smoke detector to positive (+) terminal of the zone. NAPCO Security Systems GEM-P9600 Installation Instructions...
Page 47
When a closing report is successfully received, the central station will acknowledge by returning a kissoff signal. When the kis- soff is received by the communicator, a 2-second ringback tone will sound at the keypad. Start Exit Delay After Ringback will cause the exit delay to start after the ringback sounds. NAPCO Security Systems GEM-P9600 Installation Instructions...
Page 48
Removing a keypad from the wall causes a similar system trouble indication. The keypad will display “E11-NN BURG KPD TAMPER”, where “NN” denotes the keypad number. Press the button to silence the sounder (“SYSTEM READY” will display). To manually NAPCO Security Systems GEM-P9600 Installation Instructions...
Page 49
In the event of a memory corruption, the loss of the system clock will occur and a message ‘SET TIME / DATE” will be displayed on the GEM-RP1CAe2 keypad. The message will remain until the Time and Date have been re-programmed. NAPCO Security Systems GEM-P9600 Installation Instructions...
Page 50
Program to send a “402” closing code (for Ademco Point ID modem format) in place of a “401” code. Trouble An abnormal zone condition (a break in a normally-closed loop; a short on a normally-open loop; or either on an end-of-line- resistor supervised loop) when disarmed. NAPCO Security Systems GEM-P9600 Installation Instructions...
Page 51
Two-Wire Smoke Detectors See Smoke Detectors Unvacated Premises: Convert from Away to Stay based on no egress through exit door. Default is enabled. (GEM-P9600 panel-- This feature is AUTOMATIC INTERIOR BYPASS). The panel uses the existing programmable feature "Auto Interior Bypass". This feature must be enabled in CP-01 installations.
Page 52
Aux. Output, Fire Output or Keypad Sounder on Alarm programmed) there will not be any indication on the keypad. If an Audible out- put is programmed, the keypad will flash the red Armed LED and display “ALARM” followed by the zone description. Note: Do not program a Day Zone as a 24-Hour Zone. NAPCO Security Systems GEM-P9600 Installation Instructions...
Should removal of the circuit board be necessary, use this wiring legend to relocate wire leads to their proper terminals. Enter wire identification number or color code in WIRE NUMBER column and enter wire function in DESCRIPTION col- umn (optional). TERMINAL WIRE NO. DESCRIPTION NAPCO Security Systems GEM-P9600 Installation Instructions...
MODE ACTIVATE DOWNLOAD DISPLAY RF XMITTER STAT Minimum level required to access function RELAY CONTROL Level 3 code with appropriate option Requires dealer code Not available in GEM-RP2ASe2/GEM-K2AS keypads Initial Configuration only; suppressed thereafter NAPCO Security Systems GEM-P9600 Installation Instructions...
MODE ACTIVATE DOWNLOAD DISPLAY RF XMITTER STAT Minimum level required to access function RELAY CONTROL Level 3 code with appropriate option Requires dealer code Not available in GEM-RP2ASe2/GEM-K2AS keypads Initial Configuration only; suppressed thereafter NAPCO Security Systems GEM-P9600 Installation Instructions...
Page 57
ZN# XMIT#+CS P ZN01- 000000:0-0 KF A XMIT#+CS OP 01-0 000000:0 00 ENTER DATE (_ / / ) ENTER TIME (_ : DIRECT ADDRESS Press button DEALER CODE PROGRAM MODE (at any time) 456789 NAPCO Security Systems GEM-P9600 Installation Instructions...
Page 59
Return Jumper JP5 * from Pins 2-3 to Pins 1-2 (“SYSTEM READY”) * JP5 is located at the top-right corner of the circuit board. ** If a Compatibility Number other than “0000” is programmed, “OLD COMPAT# XXXX” is displayed. NAPCO Security Systems GEM-P9600 Installation Instructions...
(3905 · · 3 · · · · ·)* (3905 · 4 )** Unvacated Premises. Convert from Away to Stay based on no egress through exit door …default is enabled. (GEM-P9600 2421, Bit 0 panel--This feature is AUTOMATIC INTERIOR BYPASS).
Page 62
• At least one Exit/Entry zone must be programmed for each area. (SIA CP-01 Specification 4.2.1) • The GEM-P9600 control panel and at least one GEM-RP1CAe2/GEM-K1CA , GEM-RP2ASe2/GEM-K2AS or a GEM-RP3DGTL/GEM-K3DGTL must be installed. • The following optional accessories support the SIA False Alarm Reduction (FAR) classification, and may be used if desired: GEM-EZOUT8, GEM- RB3008, GEM-RM3008, GEM-EZM8, GEM-EZM4/8, GEM-RECV8/16/32, GEM-TRANS2, GEM-PIR, GEM-SMOKE, GEM-HEAT, GEM-KFOB.
Page 63 GEM-P9600 FACTORY DEFAULT DESCRIPTION The Factory Program of the GEM-P9600 will change with the release of the new version that complies with Security Industry As- sociation False Alarm Reduction Control Panel-01 Standard (SIA FAR CP-01). Out of Box Panel Operation (After CP-01 Changes)
Le present appareil numerique n’emet pas de bruits radioelectriques les depassant les limites applicables aux appa- reils numeriques de Ia classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le Ministere des Communications du Canada. NAPCO Security Systems GEM-P9600 Installation Instructions...