Download Print this page

Gemini GEM-P800 Installation Instructions Manual page 27

Control panel/communicator
Hide thumbs Also See for GEM-P800:

Advertisement

E1

RED
RECHARGEABLE
BATTERY
12 VDC 4AH OR 7AH
E2
BLACK
COLD WATER GROUND
CONNECTION
USE ONLY COLD-WATER
PIPE OR BURIED GROUND
ROD. USE AT LEAST #16
AWG WIRE.
2.2K
(E)
EZ
Zone
GOLD
RED
TM
Doubling
RED RED
EARTH
Resistors
GROUND
3.9K
(Z)
(1)
ALL ZONE RESISTORS MUST BE INSTALLED,
EVEN IF ZONE IS NOT USED.
(2)
COMBINED STANDBY = KEYPAD CURRENT +
AUX POWER CURRENT + FIRE POWER + PGM
CURRENT.
(3)
24 HOUR STANDBY REQUIRES A 7AH BAT-
TERY.
Wi850a
page 27
GEM-P800 WIRING DIAGRAM
(REFER TO INSTALLATION INSTRUCTIONS WI850)
RESIDENTIAL BURG (4 HOUR STANDBY)
COMBINED STANDBY = 500 mA
RESIDENTIAL FIRE (4 HOUR STANDBY)
COMBINED STANDBY = 500 mA
RESIDENTIAL FIRE (24 HOUR STANDBY)
COMBINED STANDBY = 120 mA
1
2
+3
-4
+5
+6
-7
+8
16 VAC 20 VA
FIRE
TRANSFORMER
PWR
NAPCO TRF12
(OR EQUIVALENT
SEE WI850).
Class 2
Transformer.
DO NOT
connect to
switched
outlet.
(Z)
(Z)
(Z)
(1)
ZONE 4
ZONE 5
ZONE 6
(E)
(E)
(E)
2.2K EOLR
ZONE 1
ZONE 3
ZONE 2
Normally Open Zone Wiring
(Z)
Wire the normally open contact
4-Wire Fire Wiring
as shown (Zone 4). Program
ZONE 4
the zone for Open Circuit [06]
operation.
(E)
ZONE 1
This equipment should be installed in accordance with Chapter 2
of the National Fire Alarm Code, ANSI/NFPA 72-1993 (National
Fire Protection Association Batterymarch Park, Quincy MA
02269). and local codes. Information describing proper installa-
BELL = 2.0 AMP
tion, operation, testing, maintenance, evacuation planning, and
repair service is to be provided with this equipment. UL Listed
(2)
Energy Cable is required.
BELL = 65 mA
(3)
ALL OUTPUTS ARE CURRENT LIMITED
BELL = 95 mA
-9
+10 -11 +12 -13
14
15
FIRE
BELL
GND
+PWR
GND GREEN
PGM
(-)
REMOTE BUS
+
+
+
GEM-RP8
+

+
GEM-RECV-XP8
.
.
12
2.2K EOLR
(E)
+PWR
(SUPERVISED)
(E)
FT2200
GEM-P800 Terminals
RED
Power
Power
In (+)
Out (+)
BLACK
Power
Power
Out (-)
In (-)
BROWN
Fire Loop
Fire Loop
BROWN
Out
In
16
17
18
19
TIP
RING
TIP
RING
TELCO
PHONE
To RJ31X
(Supervised)
WARNING
TO PREVENT RISK
OF ELECTRIC SHOCK
DISCONNECT TELEPHONE
LINES PRIOR TO SERVICING
8
Fire Power
Ground
7
8
Fire Power
9
Fire
27
Tuesday, September 16, 1997 08:01

Advertisement