To replace the components, reverse the removal procedure.
IMPORTANT:
devices. The batteries charge to:
•
80 percent of their capacity within 3 hours
•
100 percent of their capacity within 48 hours
Testing the new battery module
After installing the new battery module, press the Test/Alarm Reset button to initiate a self-test
self-test" on page 41).
IMPORTANT:
IMPORTANT:
devices. The batteries charge to:
80 percent of their capacity within 3 hours
•
100 percent of their capacity within 48 hours
•
If the installation has been successful, the Battery Fault LED is not illuminated. If the installation has not
been successful, the Battery Fault LED illuminates. If this occurs, repeat the UPS battery replacement
procedure (on page 46), and check the battery terminal connections. If the Battery Fault LED is still
illuminated, see "LED and audible alarm troubleshooting
For the location of buttons, see "UPS front panel controls (on page 8)."
For the location of LEDs, see "UPS front panel LED indicators (on page 8)."
Replacing the UPS
To remove the UPS:
Power down all attached load devices.
1.
Charge the batteries for at least 24 hours before supplying backup power to
The UPS does not execute a self-test until the batteries are 90 percent charged.
Charge the batteries for at least 24 hours before supplying backup power to
("LED
troubleshooting" on page 52)."
("Initiating a
Maintenance 47