Configuring The Ups - HP R3000 User Manual

Hide thumbs Also See for R3000:
Table of Contents

Advertisement

NOTE:
the On button.
Button
Assertion
time
On
0.5
seconds
Off
3 seconds
Self Test
0.5
seconds
3 seconds
Battery
0.5
Start
seconds
Battery
3 seconds
Start and
On
On and
3 seconds
Self Test

Configuring the UPS

The UPS automatically detects the number of ERMs connected.
If the On and Off buttons are simultaneously pressed, the Off button has priority over
Audible alarm
Every 0.5
seconds until the
button is
released
Every 0.5
seconds until the
button is
released
Continuously
Continuously
Continuously
Mode before
Utility
assertion
present ?
Standby
Yes
Operate
Yes
Auto-Bypass
Yes
Converter Off
Yes
Operate
Yes
Standby
Yes
Battery
No
Auto-bypass
Yes or No
Any
Yes or No
Any
Yes or No
Any
Yes or No
UPS off
No
Any
Yes or No
Action
Energizes the load and
resets the bypass entry
count to 0
Resets the bypass entry
count to 0
Clears the UPS On audible
alarms, resets the bypass
entry count to 0, and
attempts to transfer to
Operate mode
Clears the UPS On audible
alarms, resets the bypass
entry count to 0, and
attempts to transfer to
Operate mode
Transfers to Standby
mode, and power to the
load ceases
No action
Powers down the UPS, and
power to the load ceases
Transfers to Standby mode
or Converter Off mode,
and power to the load
ceases
Silences audible alarms
after 0.5 seconds
Initiates a self-test
No action
Transfers to battery power,
and begins powering the
load
Enters or exits
Configuration mode
UPS operations 40

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

R/t3000Pavilion t3000 - desktop pc

Table of Contents