Initiating A Self-Test - HP R3000 User Manual

Hide thumbs Also See for R3000:
Table of Contents

Advertisement

In Configure mode, the LED front panel display changes function to enable modification of the UPS
parameters. Each LED is associated with a different parameter.
Available settings
Nominal voltage
setting
Wiring fault setting
NOTE:
be manually enabled.
To change the UPS configuration parameters:
Place the UPS in Configure mode (on page 39).
1.
The LEDs associated with the currently configured parameters illuminate. A flashing cursor indicates
where you are in the configuration process as you scroll through the available settings.
Press the On button to scroll through the options. Each time the On button is pressed, the audible
2.
alarm sounds.
If the On button is pressed and the UPS does not respond, the UPS is in Operate mode (on page
3.
38). Start over with step 1.
Press the Off button once to toggle the selected option on or off.
4.
Repeat steps 2 and 3 for each option.
5.
To save the configuration settings and exit Configure mode, press and hold the Test/Alarm Reset
6.
button for 3 seconds.
NOTE:
has not been pressed, any new selections are not saved.
For the location of buttons, see "UPS front panel controls (on page 8)."
For the location of LEDs, see "UPS front panel LED indicators (on page 8)."

Initiating a self-test

To initiate a self-test, press and hold the Test/Alarm Reset button
for three seconds.
If the UPS detects a problem, the appropriate LED
illuminates and an audible alarm may sound.
Parameter
Associated LED
100/204 Nom
Self Test
110/220 Nom
Battery Fault
120/230 Nom
Site Wiring Fault
127/240 Nom
Overtemperature
Wiring fault
Overload
For high voltage UPSs, the Site Wiring Fault function is disabled by default, but can
Configure mode times out after 2 minutes of inactivity. If the Test/Alarm Reset button
Explanation (when LED is illuminated)
Nominal output voltage is 100 V for a low
voltage model and 204 V for a high voltage
model
Nominal output voltage is 110 V for a low
voltage model and 220 V for a high voltage
model
Nominal output voltage is 120 V for a low
voltage model and 230 V for a high voltage
model
Nominal output voltage is 127 V for a low
voltage model and 240 V for a high voltage
model
Audible alarm will sound when ground is
missing or line and neutral connections are
reversed
("UPS front panel
("UPS front panel LED
indicators" on page 8)
controls" on page 8)
UPS operations 41