Overload Condition; Checksum Failure Error; Ups Does Not Start; Low Battery Shutdowns - HP R3000 User Manual

Hide thumbs Also See for R3000:
Table of Contents

Advertisement

Overload condition

All the load LEDs are illuminated.
Action:
Power down the UPS
1.
Remove one or more load devices to reduce the power requirements.
2.
Wait at least 5 seconds and restart the UPS.
3.
If the condition persists, verify that the load devices are not defective.
4.

Checksum failure error

A Checksum failure error occurs when executing a bad load sequence, or having an incorrect EEPROM
map while loading software through the serial or USB port.
Action:
Rerun the firmware upgrade.
1.
If the condition persists, contact an HP authorized service representative.
2.

UPS does not start

Action:
Be sure that the power cord is plugged in to a utility power receptacle.
1.
Check the power source at the utility power receptacle.
2.

Low battery shutdowns

Ungraceful shutdown of attached servers occurs when the UPS is in a low battery condition.
Action:
Verify that the power management software is not delaying the shutdown of attached servers when
1.
the UPS is in a low battery condition.
Allow the UPS batteries to charge for 24 hours.
2.
If the Battery Fault LED is red, replace the batteries
3.
46).

UPS does not provide the expected backup time

Action:
If the Overload LED
1.
devices to reduce the power requirements.
Power down the UPS
2.
Allow the UPS batteries to charge for 24 hours.
3.
Initiate a self-test
4.
("Powering down the
("UPS front panel
controls" on page 8) is illuminated, remove one or more load
("Powering down the
("Initiating a
self-test" on page 41).
UPS" on page 42).
("UPS battery replacement
UPS" on page 42).
procedure" on page
Troubleshooting 57

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

R/t3000Pavilion t3000 - desktop pc

Table of Contents