Sensing Edge Switch Installation
Figure 10 shows an example of a typical sensing edge installation. Left hand side is shown but
right hand is a mirror image of this.
1A) If wiring from sensing edge switch to operator is coiled cord or 2 wire jacketed cord:
•
Install junction box 12" above the center of the door opening on same side as
sensing switch.
•
Secure one end of cord to junction box using a cable clamp.
1B)
If connection is to be made through a take up reel cord: NON-MONITORED EDGE ONLY.
•
Install on same side as sensing edge switch and above door opening and
slightly to the side.
•
Install junction box adjacent to take up reel and route the stationary cord from
the reel to the box and secure with a cable clamp.
2)
Secure other end of cord (straight, coiled or reel) to sensing edge switch
enclosure using a cable clamp.
3)
Connect wires of cord to sensing edge switch using wire nuts or other suitable
wire connectors.
4)
Run a straight 2 wire cord from the junction box to the operator electrical box.
•
Secure using cable clamp on each end.
5)
Join wires in cord from operator to wires in cord from switch using wire nuts or
other suitable wire connectors.
9A)
Non-Monitored sensing or reversing edge connects to terminal strip using N-O
Safety inputs. See Fig. 9A .
Monitored sensing or reversing edge connects to Timer-Close Module terminals as
9B)
shown in Fig. 9B .
9C)
Monitored sensing or reversing edge (no monitored Safety-T-Beam®) using the
Monitored Edge Interface Module (OPAKMEIGX.S) connects to ODC STB terminals as
shown in Fig. 9C .
7)
Operate the door to make certain cord is free to travel and does not become
snared during door opening or closing.
•
Check sensing edge switch for proper operation.
WARNING:
Actuating the operator using constant contact on the CLOSE
button will override external reversing devices, including sensing edges or
reversing edges.
GCL-GCX
Counter Door Operator
www.geniecompany.com
CONTROL SIGNA
Figure 9A
TERM NAL STR P
TERMINAL STRIP
NOTE: Do not connect
VER
N-O
REVERSE
a 2-wire monitored
semsing edge switch
to these termiinals.
Figure 9B
MON
NOTE : Monitored 2-wire
EDGE
sensing or reversing
edge can
only be used
in combination with a
Timer-Close Module.
ODC
Figure 9C
STB
NOTE: Monitored
sensing edge connects
to main circuit board
ODC STB terminals using
optional OPAKMEIGX.S
INTERFACE MODULE.
Figure 10
VER
N-O
REVERSE
SENSING EDGE SWITCH
TIMER-CLOSE MODULE
GND
TERMINAL STRIP
SENSING EDGE SWITCH
MAIN CIRCUIT BOARD
ODC
STB
SENSING EDGE SWITCH
INTERFACE
MODULE
08-12
5.6