Heat & Glo Escape-42DV Owner's Manual page 27

Hide thumbs Also See for Escape-42DV:
Table of Contents

Advertisement

Top Vent - Vertical Termination
No Elbow
Note: A fl ue restrictor can only
be used in vent runs that in-
clude no elbows and exceed
30 ft. total of straight vertical.
Figure 7.6
Two Elbows
Note: Must have a 24 inches mini-
mum vertical vent before attaching
any elbow to the unit.
Note: A fl ue restrictor can only
be used in vent runs that in-
clude no elbows and exceed
30 ft. total of straight vertical.
Figure 7.7
V
1
V
2
H
Heat & Glo • Escape-42DV • 2052-900 Rev. Y • 11/11
FLUE
RESTRICTOR
V
1
2 ft.
610 mm
3 ft.
914 mm
4 ft.
1.2 m
5 ft.
1.5 m
6 ft.
1.8 m
V
+ V
1
2
*No specifi c restrictions on this value EXCEPT
V
+ V
+ H
1
2
1
After V
= 6 ft., then H
1
V
1
V
= 50 ft. Max. (15.2 m)
1
V
= 3 ft. Min. (914 mm)
1
FLUE RESTRICTOR
H
1
1 ft.
305 mm
3 ft.
914 mm
4 ft.
1.2 m
9 ft.
2.7 m
12 ft.
3.7 m
+ H
= 50 ft. (15.2 m) Max.
1
cannot exceed 60 ft. (18.3 m).
Max.= V
x 2
1
1
1
V
2
*
*
*
*
*
27

Advertisement

Table of Contents
loading