The Chimney - Harman Super-Magnum Owner's Manual

Coal stoker stove
Table of Contents

Advertisement

Super-Magnum Coal Stoker Stove
Hole with a minimum
clearance of 18" (450 mm)
between connector and wall.
AN APPROVED CANADIAN
WALL PASS-THROUGH
D. The Chimney
This unit must be installed into a chimney approved for use
with solid-fuel appliances. In the U.S., it must be connected to
(1) a prefabricated chimney complying with the requirements
for Type HT chimneys in the Standard for Chimneys, Factory-
Built, Residential Type and Building Heating Appliances, UL
103, or (2) a code-approved masonry chimney with a flue
liner.
In Canada, this unit is listed for use with prefabricated
chimneys tested and listed to the high temperature (650
degrees C) chimney standard, ULC S-629, or with a code
approved masonry chimney.
For mobile homes, (US only) it must only be installed with
prefabricated chimney systems, including the installation
components, tested to use in mobile homes; the diameter
should match the diameter of the flue collar opening
The minimum recommended height for any chimney is 16
ft. (4.8 m) above flue collar height. For non-mobile home
installations, a round flue (either masonry or approved
prefabricated), of either 6" (150 mm), 7" (180 mm) or 8"
(200 mm) may be used. For square or rectangular masonry
chimneys, nominal sizes of 8" x 8" or 8" x 12" (200mm x 200
mm, 200 mm x 300 mm) may be used.
Codes require that solid-fuel chimneys extend 3 ft. (0.9 m)
above the highest point at which they exit from the roof. Then,
the chimney must extend 2 ft. (6 m) above the highest point
within a 10 ft (3 m) radius. Thus, the 3 foot, 2 foot, 10 foot
rule: 3ft. - Above roof exit point
2ft. - Higher than anything within-
10ft. of the chimney.
12
Do Not Burn Wet Coal!
Non-combustible cover, one
side only. If two covers are
used, each must be mounted
on non-combustible spacers
at least 7/8" (21mm) away
from the wall.
1" (25mm)
Clearance
Closest
Combustible
Material
Minimum 12" (300mm)
to Combustibles
AN APPROVED U.S.
WALL PASS-THROUGH
Do not connect this unit to a chimney flue servicing
another appliance.
NOTE: The restriction of not venting more than one appliance
to the same flue applies to the U.S. specifically. While it is not
recommended that you use the same chimney for more than
one appliance, in Canada certain exceptions may be made.
Be sure to contact your building code inspection official to
see if this option is allowed in your area, and to find out the
specific requirements for such an installation.
More Than 10 ft. (3m)
10 ft. (3m)
2 ft. (0.6m) min.
Ridge
Chimney
The 3-foot, 2-foot, 10 foot rule
Minimum 2" (50mm)
Clearance to Brick
Minimum 12"
Liner
(300mm) to Brick
Fire Clay
Thimble
Chimney
Connector
Masonry Chimney Built to
NFPA 211 Specifications.
Height Necessary
Above Any Roof Sur-
face Within 10ft. (3m)
3ft. (0.9m)
minimum
above
exit
point
3-90-02702R6_03/13