B. Chimney Diagram
Sidewalk
V
=Vent Terminal
Figure 4.10
Requirements for Terminating the Venting
• Venting terminals must not be recessed into a wall
or siding.
• Only PL vent pipe wall pass-through and fire stops
should be used when venting through combustible
materials.
• Always take into consideration the effect the
prevailing wind direction or other wind currents will
cause with flyash and /or smoke when placing the
termination.
In addition, the following must be observed:
A. The clearance above grade must be a minimum of 12".
B. The clearance to a window or door that may be opened
must be a minimum of 48" to the side and 48" below the
window/door, and 12" above the window/door. (with
outside air installed, 12" to side and below)
C. A 12" clearance to a permanently closed window is
recommended to prevent condensation on the window.
D. The vertical clearance to a ventilated soffit located above
the terminal within a horizontal distance of 2 feet (60 cm)
from the center-line of the terminal must be a minimum
of 18".
E. The clearance to an unventilated soffit must be a
minimum of 12".
F. The clearance to an outside corner is 11" from center of
pipe.
G. The clearance to an inside corner is 12".
H. A vent must not be installed within 3 feet (90 cm) above
a gas meter/regulator assembly when measured from
the horizontal center-line of the regulator.
15
Inside Corner
Detail
Fixed
Closed
Openable
Openable
A
=Air Supply Inlet
Harman® • P-Series Installation Manual_R8 • 2014 - ___ • 04/15
Fixed
Closed
=Area where termination is not permitted
I. The clearance to service regulator vent outlet must be a
minimum of 6 feet.
J. The clearance to a non-mechanical air supply inlet to the
building or the combustion air inlet to any other appliance
must be a minimum of 48".
K. The clearance to a mechanical air supply inlet must be a
minimum of 10 feet. (with outside air installed, 6 feet)
L. The clearance above a paved sidewalk or a paved
driveway located on public property must be a minimum
of 7 feet.
M. The clearance under a veranda, porch, deck or balcony
must be a minimum of 12 inches. (B. also) The clearance
to vegetation and other exterior combustibles such
as mulch is 36" as measured from the center of the
outlet or cap. This 36" radius continues to grade or
a minimum of 7 feet below the outlet.
Certain Canadian and or Local codes or regulations may
require different clearances.
A vent shall not terminate directly above a side-walk or
paved driveway which is located between two single family
dwellings and serves both dwellings.
Only permitted if veranda, porch, deck, or balcony is fully
open on a minimum of 2 sides beneath the floor.
See NFPA 211 for more installation clearance reductions
when using outside air. where passage through a wall,
or partition of combustible construction is desired,
the installation shall conform to CAN/CSA-B365. (if in
Canada)
Porch or
Deck
Openable
or Fixed
3-90-436168i