40 series residential oil burners, equipped with electronic air shutter
Table of Contents

Advertisement

SINGLE
LINE
(GRAVITY
FEED
SYSTEM)
A) The burner is shipped configured for use in single line applications. No changes to the oil pump are required
for use in single line applications.
NOTE:
If the pump cover (1) is removed for any reason, be sure the O-ring (2), is properly seated in the pump
cover (1) before re-attaching the pump cover to the pump housing.
SINGLE
LINE
SYSTEM-PIPE
LENGTHS
H
3/8" OD
1/2" OD
FT
M
FT
M
FT
M
1.5
0.5
33
l0
65
20
3.0
1.0
65
20
130
40
5.0
1.5
130
40
260
80
6.5
2.0
195
60
325
100
B) Connect the pipe connector to the SUPPLY PORT (5) of the
pump.
Attach
the NPT
adapter
to the
pipe
connector.
Attach the required piping to this pipe adapter. Be sure that
the plug in the RETURN PORT (7) is tightened securely.
NOTE: Do not exceed pipe lengths indicated in
chart.
TWO LINE (LIFT
SYSTEM)
1
P
NOTE: Do not exceed pipe lengths indicated in
chart.
2 LINE (LIFT)
SYSTEM-PIPE
LENGTHS
H
3/8" OD
1/2" OD
FT
M
FT
M
FT
M
0.0
0.0
ll5
35
330
100
1.5
0.5
100
30
330
100
3.0
1.0
80
25
330
100
5.0
1.5
65
20
295
90
6.5
2.0
50
15
230
70
9.5
3.0
25
8
100
30
11
3.5
20
6
65
20
A) If a two-line system is required, install the By-pass plug provided. The by-pass plug is installed in the return
port of the pump. A 2.5-1ran hexagonal key provided with the by-pass plug is to be used to install the plug.
DO NOT use an inch size hexagonal key; damage to the by-pass plug may result. When operating on a two-
Standard
40 F3-F5 I-O manual
Rev4
l.doc
Page 12 of 12