Burner Adjustment Tables - Riello 40 F5 Installation & Operating Manual

40 series residential oil burners, equipped with electronic air shutter
Table of Contents

Advertisement

BURNER
ADJUSTMENT
TABLES
NON-RETROFIT
APPLICATIONS
If this burner
is being installed
in a packaged
unit (i.e. Burner
comes with a boiler or furnace),
follow the
installation
and set-up
instructions
supplied
with the heating
appliance,
as settings
will differ from those
shown in this manual.
MODEL
F3 BURNER
SETUP
CHART
ACTUAL
FIRING
RATE
5% ±
US GPH
0.50
0.60
0.75
0.80
0.95
NOZZLE
SIZE
GPH
.40 x 60°/80 °
.50 x 60°/80 °
.60 x 60°/80 °
.65 x 60°/80 °
.75 x 60°/80 °
PUMP
PRESSURE
PSI
BAR
160
11.0
150
10.4
150
10.4
150
10.4
160
11.0
TURBULATOR
SETTING
0.0
0.5
1.5
2.0
3.0
MODEL
F5 BURNER
SETUP
CHART
AIR
DAMPER
SETTING
2.3
2.7
3.4
3.6
4.3
ACTUAL
FIRING
RATE 5% ±
US GPH
0.75
0.85
1.00
1.10
1.25
1.50
1.65
NOZZLE
SIZE
GPH
PUMP
PRESSURE
PSI
BAR
TURBULATOR
SETTING
.60 x 60/80
°
145
10
0.0
.65 x 60/80
°
145
10
0.5
.85 x 60/80
°
145
l0
1.0
1.00 X 60/80 °
145
10
2.0
1.10 x 60/80
°
145
10
2.5
1.25 x 60/80 °
145
10
3.0
1.35 X 60/80 °
145
10
4.0
AIR DAMPER
SETTING
2.25
2.5
2.75
3.0
3.5
4.25
6.0
NOTE:
The above
set up charts are a starting
point
only. The burner
and appliance
must
be properly
set
up using proper
combustion
testing
equipment.
Note: any approved
oil burner nozzle type, angle and manufacturer
maybe used, as long as input
is corresponding
the correct BTU/hr.
or US gph input rating of the appliance.
COMBUSTION
CHAMBER
Follow the instructions
furnished
by the boiler/furnace
manufacturer.
Size retrofit application
according
to the
appropriate installation codes (e.g. CSA B 139 or NFPA #31).
Standard
40 F3-F5 I-O manual
Rev4
l.doc
Page 15 of 15