Refrigeration Cycle; Motor And Lubricating Oil; Cooling Cycle - Carrier 19XRV Start-Up, Operation And Maintenance Instructions Manual

Hermetic centrifugal liquid chillers with pic iii controls 50/60 hz hfc-134a
Table of Contents

Advertisement

REFRIGERATION
CYCLE
The compressor
continuously
draws refrigerant
vapor from
the cooler at a rate set by the amount of guide vane opening or
compressor
speed.
As the compressor
suction
reduces
the
pressure in the coolel: the remaining
refrigerant boils at a fairly
low temperature
(typically 38 to 42 F [3 to 6 C]). Tile energy
required for boiling is obtained from the water flowing through
the cooler tubes. With heat energy removed, the water becomes
cold enough to use in tin air conditioning
circuit or for process
liquid cooling.
After taking heat from the water, the refrigerant
vapor is
compressed.
Compression
adds still more heat energy, and the
refrigerant
is quite wmm (typic_flly 98 to 102 F [37 to 40 C])
when it is discharged
t]om the compressor
into the condensel:
Relatively
cool (typically
65 to 90 F [18 to 32 C]) water
flowing into the condenser
tubes removes heat from the refrig-
erant and the vapor condenses
to liquid.
The
liquid
refi'igerant
passes
through
orifices
into the
FLASC (Flash Subcooler)
chamber
(Fig. 3). Since the FLASC
chamber
is at a lower plessure,
part of the liquid refrigerant
flashes to vapol: thereby
cooling
the lemaining
liquid. The
FLASC vapor is recondensed
on the tubes which are cooled by
entering condenser
watel: The liquid drains into a float cham-
ber between the FLASC chamber and cooler Here a float v_dve
forms a liquid seal to keep FLASC chamber
vapor from enter-
ing the coolel:
When
liquid refrigerant
passes
through
the
vMve, some of it flashes to vapor in the reduced pressure on the
cooler side. In flashing, it removes heat from the remaining
liq-
uid. The refrigerant
is now at a temperature
and plessure
at
which the cycle began.
MOTOR
AND LUBRICATING
OIL
COOLING
CYCLE
The motor and the lubricating
oil are cooled by liquid re-
frigerant
taken
from
the bottom
of the condenser
vessel
(Fig. 3). Refrigerant
flow is maintained
by the pressure differ-
ential that exists due to compressor
operation. After the refrig-
erant flows past an isolation
valve, tin in-line filtel: and a sight
glass/moisture
indicatol:
the flow is split between
the motor
cooling and oil cooling systems.
Flow to the motor cooling system passes through an orifice
and into the motor. Once past the orifice, the refrigerant
is
directed
over the motor by a spray nozzle.
The refrigerant
collects in the bottom of the motor casing and is then drained
back into the cooler through the motor refrigerant
di'ain line.
An orifice (in the motor shell) maintains
a higher pressure in
the motor shell than in the coolel: The motor is protected by a
temperature
sensor
imbedded
in the stator windings.
An
increase in motor winding temperature
past the motor override
set point overrides
the temperatme
capacity
control to hold,
and if the motor temperature
rises 10 ° F (5.5 ° C) above this set
point, closes
the inlet guide vanes.
If the temperature
rises
above the safety limit, the compressor
shuts down.
Refrigerant
that flows to the oil cooling system is regulated
by thermostatic
expansion
valves (TXVs). The TXVs regulate
flow into the oil/lefrigerant
plate and fralne-type
heat exchang-
er (the oil cooler in Fig. 3). The expansion
valve bulbs control
oil temperature
to the bemings. The refrigerant
leaving the oil
cooler heat exchanger
returns to the chiller coolel:
FLASC CHAMBER
CONDENSER
WATER
Ii
FLOATVAWE.
CHAMBER
DRIER
MOISTURE/
FLOW
INDICATOR
ORIFICE-
FITTING
VFD'
COOLING
ISOLATION
VALVE
THERMOSTATIC
EXPANSION
VALVE
(TXV)
UNIT
MOUNTED
VFD
(VARIABLE
FREQUENCY
DRIVE)
HEAT
EXCHANGER
SOLENOID
VALVE (OPTION)
DIFFUSER
VANE
MOTOR
COOLER
ISOLATION
VALVE (OPTION)
Fig. 3 -- Refrigerant Motor Cooling and Oil Cooling
Cycles
REFRIGERANT
LIQUID
REFRIGERANT
VAPOR
_
EFRIGERANT
LIQUID/VAPOR
F_
OIL
CHILLED
WATER

Advertisement

Table of Contents
loading

Table of Contents