Kilowatt Output; Remote Reset Of Alarms; Condenser Pump Control; Condenser Freeze Prevention - Carrier 19XRV Start-Up, Operation And Maintenance Instructions Manual

Hermetic centrifugal liquid chillers with pic iii controls 50/60 hz hfc-134a
Table of Contents

Advertisement

Kilowatt
Output
--
An output is available
on tile CCM
module [Terminal J8-1 (+) and J8-2 (-)1 to represent the power
consumption
of the chiller
Tile 4 to 20 mA signal generated by
the CCM module can be wired to the building automation
or
energy management
system
to monitor
the chiller's
energy
consumption.
Output
is 2 mA with the chiller
off. and it
varies linedy
from 4 mA (representing
0% rated kilowatt
consumption)
to 20 mA (representing
100% RATED
LINE
KILOWATFS).
The
rated
peak
kilowatt
consumption
is
configured
by the user in the VFD_CONF
display
screen by
the setting the RATED LINE KILOWATFS
fiom the machine
electrical &tta nameplate.
Remote
Reset of Alarms
--
A stan&u'd feature of the
PIC |II controls is the ability to reset a chiller in a shutdown
alarm state from a remote
location.
[f the condition
which
caused the alarm has cleared the chiller can be placed back into
a normal CCN operating
mode when the REMOTE
RESET
OPTION
(ICVC_PSWD
menu) is set to ENABLE.
A variety
of Career
Comfort
Network
software
systems
including
ComfortVIEW
TM
or Network
Sel-v'ice Tool
TM
can access the
PIC III controls
and reset the displayed
alarm.
Third party
software
from building
automation
systems
(BAS) or energy
management
systems
(EMS)
can also access
the PIC III
controls through a Carrier DataLINK rM module and reset the
fault displayed. Both methods would access the ICVC_PSWD
screen and fome the RESETALARM?
point to YES to reset the
fault condition.
[f the P[C III controls have determined
that is
safe to start the chiller the CCN MODE?
point (ICVC_PSWD
screen) can be forced to YES to place the chiller back into
norln;fl CCN operating
mode. The only exceptions
am the
following
ahums that cannot be reset from a remote location:
Aimm/Alert
STATE
100, 200,
201,
204,
206,
217-220,
233, 234, 247, and 259. To view alarm codes, refer to Trouble-
shooting
Guide,
Checking
Display Messages,
page 79. After
the alarm has been reset the PIC HI control will increment
the
STARTS IN 12 HOURS counter by one upon restart. If the limit
of 8 starts in a 12-hour period is reached (Pmstart/Alert
state
100), this must be reset at the local chiller
control
panel
(IeVC).
Condenser
Pump Control
--
The chiller
will moni-
tor the CONDENSER
PRESSURE
and may turn on the con-
denser pump if the condenser
pressure becomes too high while
the compressor
is shut down. The COND PRESS OVERRIDE
paralneter
is used to determine
this pressure
point. COND
PRESS OVERRIDE
is found in the SETUPI
display screen,
which
is accessed
from the EQUIPMENT
SERVICE
table.
The default value is 125 psig (862 kPa).
If the CONDENSER
PRESSURE
is greater than or equal to
the COND
PRESS
OVERRIDE,
and the ENTERING
CON-
DENSER
WATER temperature
is less than 115 F (46 C), the
condenser
pump will energize to try to decrease
the pressure
and Alert 151 will be generated.
The pump will turn off when
the condenser
pressure
is 3.5 psi (24.1 kPa) less than the
pressure
override
and the CONDENSER
REFRIG
TEMP is
within 3 ° F (1.7 ° C)of
the ENTERING
CONDENSER
WATER
temperature.
Condenser
Freeze
Prevention
-- This
control
_dgo-
rithm helps prevent condenser
tube freeze-up by energizing the
condenser
pump relay. The PIC III controls the pump and, by
starting it, helps to prevent the water in the condenser
fiom
freezing. The PIC III can perform this lhnction
whenever
the
chiller is not running excq)t when it is either actively in pump-
down or in pumpdown/lockout
with the fieeze
prevention
disabled.
When the chiller is off and CONDENSER
REFRIG
TEMP
is
less
than
the
CONDENSER
FREEZE
POINT,
the
CONDENSER
WATER PUMP will be energized
(Alert State
154) Howevel,
if the chiller
is in pump down, and when it
entered pump down mode the CONDENSING
REFRIG
TEMP
was
more
than 5 ° F (2.7 ° C) above
the CONDENSER
FREEZE
POINT.
the same low temperature
condition
will
generate
Alarm
State 244 trod the CONDENSER
WATER
PUMP will be energized. In either case, the fault state will clem
and the pump will turn off when the CONDENSER
REFRIG
TEMP is more than 5 ° F (2.7 ° C) above the
CONDENSER
FREEZE POINT and the entering condenser
water temperature
is greater than the CONDENSER
FREEZE POINT. If the chill-
er is in Recycle
Shutdown
Mode when the condition
occurs,
the controls will transition to a non-recycle
shutdown.
Evaporator
Freeze
Protection
--
When the EVAP-
ORATOR REFRIG
TEMP is less than the EVAP
REFRIG
TRIPPOINT
plus the REFRIG
OVERRIDE
DELTA T (config-
urable fi_m 2 ° to 5 ° F or 1.1 ° to 2.8 ° C), Alert State 122 will be
displayed, and a capacity override will occm: (See Table 7.)
When the unit is running or in recycle, if the EVAPORATOR
REFRIG
TEMP is equal to or less than the EVAP REFRIG
TRIPPOINT
(33 ° F or 0.6 ° C for watek configurable
for brine),
Protective
Limit Alarm State 232 will be displayed,
the unit
will shut down, and the CHILLED
WATER PUMP will remgfin
on. The alarm will be clem'able when the leaving chilled water
temperature
rises 5°F (2.8°C) above the CONTROL
POINT.
When the unit is off, if the EVAPORATOR
REFRIG
TEMP
is less than the EVAP REFRIG TRIPPOINTplus
1° F (0.6 ° C),
Alarm State 243 will be generated
and the CHILLED
WATER
PUMP
will be turned on. The _flmm can be reset when the
EVAPORATOR
REFRIG
TEMP rises 5 ° F (2.8 ° C) above the
EVAP REFRIG TRIPPOINT`
Tower Fan Relay Low and High
--
Low
condens-
er water temperature
can cause the chiller to shut down when
refrigerant temperature
is low. The tower fan relays, located in
the stmter, am controlled
by the PIC III to energize and deener-
gize as the pressure differential
between cooler and condenser
vessels changes. This prevents low condenser
water tempera-
turn and maximizes
chiller efficiency. The tower fan relay can
only accomplish
flris if the relay has been added to the cooling
tower temperature
controllel:
TOWER
FAN RELAY
LOW
is turned
on whenever
the
condenser
water pump is running,
flow is verified,
;rod the
difference between cooler and condenser
pressure is more than
30 psid (207 kPad) for entering condenser
water temperature
greater than 65 F (18.3 C).
TOWER FAN RELAY LOW is turned off when the condens-
er pump is off. flow is stopped, or the EVAP REFRIGERANT
TEMP
is less than the EVAP
REF OVERRIDE
TEMP
for
ENTERING
CONDENSER
WATER
temperature
less than
62 F (16.7 C), or the difference
between
the CONDENSER
PRESSURE
and
EVAPORATOR
PRESSURE
is less than
25 psi d (172.4 kPad) for ENTERING
CONDENSER
water less
than 80 F (27 C).
TOWER
FAN
RELAY
HIGH
is turned
on
whenever
the condenser
water pump
is running,
flow is verified
and
the
difference
between
EVAPORATOR
PRESSURE
and
CONDENSER
PRESSURE
is more than 35 psid (241.3 kPa)
for ENTERING
COND
WATER temperature
greater than the
TOWER
FAN HIGH SETPOINT
(SETPOINT
menu, default
75 F [23.9 C]).
41

Advertisement

Table of Contents
loading

Table of Contents