Flow Detection - Carrier 19XRV Start-Up, Operation And Maintenance Instructions Manual

Hermetic centrifugal liquid chillers with pic iii controls 50/60 hz hfc-134a
Table of Contents

Advertisement

L,_
3 00in
............
_-J
CONNECTOR
_-_-_
_----
_i6,35" mm)(762 mm)
, .-
RECEPTACLE
NPT
WATERPROOF
SEAL
Fig. 11 -- Control
Sensors (Temperature)
3.6" TUBE
LENGTH
(90MM)
\EATSHR,NK\
2-CONDUCTOR
CABLE
Fig. 12 -- Temperature Sensor Used
With Thermal Well
1/4" SAE FEMALE
FLARE
WITH
INTEGRAL
SCHRADER
DEFLATOR
Fig. 13 -- Control Sensors
(Pressure Transducers, Typical)
A Refrigerant
Saturation Temperature
sensor (thermistor)
is
located
in the base
of the evaporator,
sensing
refrigerant
temperature
directly.
Evaporator
and
condenser
water
side
differential
pressure
transducers
_u'e not stan&trd and are not
required.
The [CVC software
uses the evaporator
saturation
refrigerant
temperature
in place of diffferential pressure
flow
detection to provide evaporator
fieeze protection.
Approach
temperatures
are shown in the HEAT_EX
scleen.
EVAPORATOR
APPROACH
is
defined
as
LEAVING
CHILLED
WATER temperature
minus EVAP SATURATION
TEMP
(from
the temperature
sensor).
CONDENSER
AP-
PROACH
is defined
as CONDENSER
REFRIG
TEMP
(derived
from condenser
pressure)
minus
LEAVING
CON-
DENSER
WATER temperature.
When the chiller is running,
the displayed
v_due for either approach
will not be less than
0.2 ° F (0.1 o C). If either approach
value exceeds the value con-
figured
in the SETUPI
screen,
the corresponding
Approach
Alert message will be entered into the Alert Histo U table.
FLOW DETECTION-
Flow detection
for the evaporator
and condenser
is a required condition
for stm-t-up and used in
the freeze protection
safety. Flow and no flow conditions
are
detected
from a combination
of several measurements.
The
usage of waterside
diffelential
pressme
measmements
is not
standard or required.
Positive
detemrination
of flow on the evaporator
side is
made if the following conditions
ale true: (1) the EVAP SATU-
RATION
TEMP
reads higher than 1° F (0.6 ° C) above the
EVAP REFRIG
TRIPPOINT.
and (2) EVAP REFRIG
TEMP
(determined
from the Evaporator
Pressure
sensor) is greater
than the EVAP REFRIG
TRIPPOINT.
(If the unit is in Pump-
down or Lockout mode, conditions
(1) and (2) ;ue not required
to establish
flow.) On the condenser
side, positive detemrina-
tion of flow is made if the following
conditions are tree: (1) the
CONDENSER
PRESSURE
is less than 165 psig (1139 kPa),
and (2) CONDENSER
PRESSURE
is less than the configured
COND
PRESS
OVERRIDE
threshold
by more
than 5 psi
(34.5 kPa). In addition,
if the waterside
differentkd
pressure
measurement
option is enabled, the watel_ide
pressure differ-
entials (cooler and condenser)
must exceed
their respective
configured cutout thresholds.
A No Flow determination
is made on the evaporator
side if
(1) the EVAP SATURATION
TEMP
reads lower than 1° F
(0.6 ° C) below the EVAP REFRIG
TRIPPOINT.
or (2) EVAP
REFRIG
TEMP
(determined
from the Evaporator
Pressure
sensor) is less than the EVAP REFRIG
TRIPPOINT
and the
EVAPORATOR
APPROACH
exceeds
the configured
EVAP
APPROACH
ALERT
threshold.
On the condenser
side, a
No Flow
determination
is also made
if the CONDENSER
APPROACH
exceeds
the configured
COND
APPROACH
ALERT threshold
and either (1) CONDENSER
PRESSURE
exceeds
165 psig (1139 kPa) or (2) CONDENSER
PRES-
SURE
exceeds
the configured
COND
PRESS
OVERRIDE
threshold by more than 5 psi (34.5 kPa). In addition, if the wa-
ter side
differential
pressure measurement
option is enabled, a
differential
below
the configured
EVAP or COND
FLOW
DELTA P CUTOUT
v_due is sufficient to establish No Flow in
either heat exchangel:
If No Flow (for either cooler or condenser)
has been deter-
mined, and subsequently
conditions
change such that neither
conditions
for Flow nor No Flow are _dl satisfied, the determi-
nation will remain No Flow.
In the standard [CVC setup, waterside differential
pressure
indication
is disabled by default. The displays
for CHILLED
WATER DELTA P and CONDENSER
WATER DELTA P in
the HEAT_EX
screen will show "*****".
In order to enable
the option
and display
a value,
change
FLOW
DELTA
P
DISPLAY
to ENABLE
in the SETUPI
scleen. Pairs of pres-
sure transducers
may be connected
to the CCM at temrinals
J3 13-24 in place of the standard resistors and jumpers to deter-
mine water-side
pressme differentials
as in the standard ICVC
configuration.
(NOTE:
If the FLOW DELTA P DISPLAY
is
enabled but the standard CCM connection
is retained, a differ-
ential value of approximately
28.5 psi (197 kPa) will _flways be
displayed.)
If watel_ide diffelential
plessure transducel_
me used, flow
is detected fi_m differential
pressure between sensors (pressure
transducers)
located in water inlet and outlet nozzles, for earl1
heat exchangeE
The thresholds
for flow determination
(EVAP
FLOW DELTA P CUTOUT.
COND FLOW DELTA P CUT-
OUT) are configured
in the SETUPI
screen. If the measured
differential
is less than the corresponding
cutout value for 5
seconds, the determination
is that flow is absent. If no flow is
detected after W_TER FLOW VERIFY
TIME (configured
in
the SETUPI
screen) after the pump is commanded
to start by
the PIC, a shutdown will result, and the corresponding
loss-of-
flow _dmm (alarm state 229 or 230) will be declared.
If the
measured
differenti_d exceeds
the Flow Delta P cutout value,
flow is considered
to be present.
Alternatively.
norm_dly open flow switches may be used for
flow indication.
In this case, inst_dl an evaporator
side flow
switch
in parallel
with a 4.3k ohm resistor
between
CCM
terminals J3 17-18, replacing the jumpel:
See page 114. For a
condenser
side flow switch do the same between CCM termi-
nals J3 23-24. If this type of flow switch circuit is used, it is
important
to perform
a zero point calibration
(with the flow
switch open).
15

Advertisement

Table of Contents
loading

Table of Contents