Clearances; Firebox Installation Instructions - Empire Comfort Systems VFD32FB0L-1 Installation Instructions And Owner's Manual

Deluxe vent-free universal fireboxes
Hide thumbs Also See for VFD32FB0L-1:
Table of Contents

Advertisement

Sidewall Clearances: The clearance from the inside of the firebox
to perpendicular combustible side wall should not be less than
6". See Figure 1.
Firebox Side and Back Clearances: The firebox outer casing side
and back flanges are zero clearance to combustibles.
Top Framing and Finishing: Combustible framing may rest on
top of standoffs. Combustible finishing materials may extend
to the top standoff screws on the front edge of the outer wrap.
See Figure 2.
FRONT FACE (SIDE)
2 X 4
HEADER
STAND OFF
FIREBOX

FIREBOX INSTALLATION INSTRUCTIONS

Any vent-free Gas Log Heater must be "For use with approved
ANSI Z21.11.2 unvented room heater."
Follow and complete the installation instructions of the gas log set
and the requirements of this firebox.
Page 4

CLEARANCES

COMBUSTIBLE
MATERIALS ALLOWED
IN SHADED AREAS
FIREBOX
(TOP VIEW)
3"
45°
MAX.
6"
PERPENDICULAR
SIDE WALL
Figure 1
COMBUSTIBLE
FINISHED WALL
OR MANTEL
FINISH WITH TRIM KIT OR
NON-COMBUSTIBLE MATERIAL
AS DESIRED.
Figure 2
Clearances to combustibles
Ceiling Clearances: The ceiling height should not be less than 42"
from the top of the hood. See Figure 3.
Mantel Clearances: Vent free firebox models must use the hood
supplied with the firebox, or one of the optional hood kits
available for each model. If a combustible mantel is installed,
it must meet the clearance requirements detailed below.
Grate Clearance: The minimum clearance between the front legs
of the grate and front edge of the firebox is 2".
Leave at least 36" clearance from the front of the firebox.
CEILING
24 ½"
42"
MIN.
(CEILING TO
TOP OF HOOD)
13"
84"
MIN.
(CEILING TO FLOOR)
3/8" COMBUSTIBLE
CLEARANCE REQUIRED
FROM TOP EDGE
OF FIREBOX
Check all fittings for leaks before lighting the gas log set.
In planning the installation for the firebox, it is necessary to
determine where the unit is to be installed and whether optional
accessories are desired. Gas supply piping should also be planned
at this time.
A gas shut off must be in this line.
12"
MAX
10"
MANTEL
COMBUSTIBLES
10"
8"
ALLOWED
22"
6 ½"
20"
5"
18"
3 ½"
16"
2"
14"
3/4"
12 ½"
11 1/2"
MIN.
0"
HOOD
FIREBOX
FACE
Figure 3