Product Description
CHAPTER 1
The 411UDAC is a fire alarm communicator with four input/channels and dual telephone lines. The four inputs use
conventional input devices. The 411UDAC accepts waterflow devices, two-wire smoke detectors, four-wire smoke
detectors, pull stations and other normally-open contact devices. The unit also supervises AC voltage, telephone line
input voltage/current, battery level and battery charger operation.
Outputs include one supplementary NAC (Notification Appliance Circuit), two programmable Form-C relays and 12
VDC resettable special application power. The 411UDAC interfaces with the public switched telephone network and
is compatible with most central station receivers. A total of fifteen popular communications formats are supported,
including the industry standard Ademco Contact ID. The communicator also contains a unique DACT option that
eliminates 'dialer runaway'. It restricts the transmission of any intermittent nuisance fault to 10 attempts in a 24 hour
period.
Accessories include the Fire-Watch 411 Series DACT Programmer (Model PRO-411) as well as the PK-411UD
®
Windows
95 based remote site programming software. The 411UDAC is supplied with a compact metal cabinet.
The digital communicator can be programmed or interrogated off-site via the public switched telephone network.
Any IBM compatible personal computer with Windows
and Upload/Download software P/N PK-411UD, may serve as a service terminal.
1.1

Product Features

• Four input/channels - three fixed Style B (Class B) and
one Style A (Class A) or Style B (Class B)
• Programmable input channels
2-wire smoke (Inputs 1 & 3 only)
pull station
normally-open contact
host panel trouble (Slave Mode)
supervisory
supervisory autoresettable
waterflow (silenceable)
waterflow (nonsilenceable)
• One Style Y (Class B) NAC (supplementary application)
• Dual telephone lines
Dual telephone line voltage detect
Alternating phone lines for 24 hour test messages
• 12 VDC operation
• 1.6 amps total system power
• Alarm Verification
• Signal Silence Inhibit
• Autosilence
• Trouble Reminder
• Trouble Resound - troubles will resound the buzzer every 24
hours at midnight until the trouble is cleared
• Optional DP-2 Dress Panel (required for Canadian
applications)
Product Description
®
411UDAC
Document #51073
3.1 or greater, with a 1200 baud Hayes

411UDAC Digital Communicator

FIGURE 1-1:
FIGURE 1-2:
Rev. D 12/09/2008
P/N 51073:D
®
compatible modem
DP-2 Dress Panel
9