Events And Default Event Codes - Fire-Lite 411UDAC Installation, Programming, Troubleshooting And Operating Instruction Manual

Fire alarm communicator
Table of Contents

Advertisement

Events and Default Event Codes

Appendix D
Note: The character 'x' in the following table refers to the input circuit number (1 - 4).
411UDAC Events
Input Circuit Functions
2-Wire Smoke
Pull Station
Contact Closure
Host Control Panel Trouble
Latching Supervisory
Autoresettable Supervisory
Silenceable Waterflow
Nonsilenceable Waterflow
Other Events
Input Circuit Fault
AC Fault
Earth Fault
Low Battery Fault
No Battery Fault
Phone Line 1 Fault
Phone Line 2 Fault
NAC Fault
Phone Number 1 Fault
Phone Number 2 Fault
System Off Normal Fault
Special Events
System Test Message
System Abnormal Test Message
Upload/Download Request
Upload Successful
Download Successful
Upload/Download Failed
Group Definitions:
Format Group 1
4+2 Ademco Express Standard, DTMF
3+1 Expanded 1800 Hz Carrier
3+1 Expanded 1900 Hz Carrier
4+1 Expanded 1800 Hz Carrier
4+1 Expanded 1900 Hz Carrier
4+2 Standard 1800 Hz Carrier
4+2 Expanded 1800 Hz Carrier
4+2 Standard 1900 Hz Carrier
4+2 Expanded 1900 Hz Carrier
Format Group 2
4+1 Ademco Express Standard, DTMF
3+1 Standard 1800 Hz Carrier
3+1 Standard 1900 Hz Carrier
4+1 Standard 1800 Hz Carrier
4+1 Standard 1900 Hz Carrier
Note that although all Expanded Mode formats communicate two digits per event, only the first digit is
programmable. The second digit cannot be changed.
80
Events and Default Event Codes
Format Group 1
Active
Restore
1x
Ex
1x
Ex
1x
Ex
FF
Ex
8x
Ex
8x
Ex
1x
Ex
1x
Ex
Active
Restore
Fx
Dx
92
93
61
A1
62
A2
63
A3
64
A4
65
A5
66
A6
6A
AA
6B
AB
6F
AF
Active
Restore
99
-
91
-
71
-
72
-
73
-
74
-
411UDAC
Format Group 2
Active
Restore
1
E
1
E
1
E
F
E
8
E
8
E
1
E
1
E
Active
Restore
F
D
9
9
6
A
6
A
6
A
6
A
6
A
6
A
6
A
6
A
6
A
Active
Restore
9
-
F
-
7
-
7
-
7
-
7
-
1400/2300 Hz ACK
2300 Hz ACK
1400 Hz ACK
2300 Hz ACK
1400 Hz ACK
2300 Hz ACK
2300 Hz ACK
1400 Hz ACK
1400 Hz ACK
1400/2300 Hz ACK
2300 Hz ACK
1400 Hz ACK
2300 Hz ACK
1400 Hz ACK
Document #51073
Rev. D 12/09/2008
Ademco Contact ID
Active and
Sensor #
Restore
111
00x
115
00x
110
00x
373
00x
200
00x
200
00x
113
00x
113
00x
Active and
Sensor #
Restore
380
00x
301
000
310
000
302
000
311
000
351
000
352
000
321
000
354
001
354
002
308
000
Active and
Sensor #
Restore
602
000
608
000
411
000
416
000
412
000
412
000
P/N 51073:D