Relay Installation; Programmable Relay - Fire-Lite 411UDAC Installation, Programming, Troubleshooting And Operating Instruction Manual

Fire alarm communicator
Table of Contents

Advertisement

Output Circuits
Relay Programming:
The relays are programmable for activation on fire alarm, host panel trouble, fire supervisory, total communica-
tion failure and DACT. Refer to "DACT Programming" on page 36. Addresses '85 - 88' are used for program-
ming relay functions and enable.

Programmable Relay

FIGURE 2-9:
Note: Relay connections may be power-limited or nonpower-limited, provided that 0.25" spacing is
maintained between conductors of power-limited and nonpower-limited circuits.
Relay 1 - Shown Programmed for Alarm,
Supervisory, or any other function except
DACT Trouble and Host Panel Trouble
(relay contacts shown in deenergized
condition with power applied to 411UDAC)
RELAY 1
RELAY 2
TB1
NO
NC
C
NO
NC
411UDAC
Document #51073
Relays automatically change to energized
condition when programmed for Trouble.
C
Relay 2 - Shown Programmed for DACT
Trouble or Host Panel Trouble (relay con-
tacts shown in energized condition with
power applied to 411UDAC)
Rev. D 12/09/2008
P/N 51073:D
27