Electronic Thermal Overload Alarm Setting - Hitachi L200 Series Instruction Manual

Single-phase input 200v class; three-phase input 200v class; three-phase input 400v class
Hide thumbs Also See for L200 Series:
Table of Contents

Advertisement

3–32
"B" Group: Fine Tuning Functions
Func.
Code
SRW Display
B001 Selection of automatic
restart mode
IPS POWR
B002 Allowable under-
voltage power failure
time
IPS Time 0001.0s
B003 Retry wait time before
motor restart
IPS Wait 0001.0s
B004 Instantaneous power
failure / under-voltage
trip alarm enable
IPS TRIP
B005 Number of restarts on
power failure / under-
voltage trip events
IPS RETRY

Electronic Thermal Overload Alarm Setting

The thermal overload detection protects the
inverter and motor from overheating due to
an excessive load. It uses a current/inverse
time curve to determine the trip point.
First, use B013 to select the torque charac-
teristic that matches your load. This allows
the inverter to utilize the best thermal
overload characteristic for your application.
The torque developed in a motor is directly
proportional to the current in the windings,
which is also proportional to the heat generated (and temperature, over time). Therefore,
"B" Function
Name /
Select inverter restart method,
four option codes:
00... Alarm output after trip,
ALM
no automatic restart
01... Restart at 0Hz
02... Resume operation after
frequency matching
03... Resume previous freq.
after freq. matching, then
decelerate to stop and display
trip info.
The amount of time a power
input under-voltage can occur
without tripping the power
failure alarm. Range is 0.3 to
25 sec. If under-voltage exists
longer than this time, the
inverter trips, even if the restart
mode is selected.
Time delay after under-voltage
condition goes away, before
the inverter runs motor again.
Range is 0.3 to 100 seconds.
Two option codes:
00... Disable
01... Enable
OFF
Two option codes:
00... Restart 16 times
01... Always restart
16
Run
Mode
Description
Edit
Torque
Constant torque
100%
80%
60%
0
5
Defaults
–FEF
–FU
Units
(EU)
(USA)
00
00
1.0
1.0
sec.
1.0
1.0
sec.
00
00
sec.
00
00
sec.
B013 = 01
Reduced
torque
B013 = 00
20
60
120
Output frequency