Hitachi L200 Series Instruction Manual page 117

Single-phase input 200v class; three-phase input 200v class; three-phase input 400v class
Hide thumbs Also See for L200 Series:
Table of Contents

Advertisement

Option
Terminal
Function Name
Code
Symbol
13
USP
Unattended Start
Protection
15
SFT
Software Lock
16
AT
Analog Input
Voltage/current
Select
18
RS
Reset Inverter
19
PTC
PTC Thermistor
Thermal Protection
20
STA
Start
(3-wire interface)
21
STP
Stop
(3-wire interface)
22
F/R
FWD, REV
(3-wire interface)
23
PID
PID Disable
Input Function Summary Table
ON
On powerup, the inverter will not resume a Run
command (mostly used in the US)
OFF
On powerup, the inverter will resume a Run
command that was active before power loss
ON
The keypad and remote programming devices
are prevented from changing parameters
OFF
The parameters may be edited and stored
ON
Terminal [OI] is enabled for current input (uses
terminal [L] for power supply return)
OFF
Terminal [O] is enabled for voltage input (uses
terminal [L] for power supply return)
ON
The trip condition is reset, the motor output is
turned OFF, and powerup reset is asserted
OFF
Normal power-ON operation
ANLG When a thermistor is connected to terminals [5]
and [L], the inverter checks for over-
temperature and will cause trip event and turn
OFF output to motor
OPEN
A disconnect of the thermistor causes a trip
event, and the inverter turns OFF the motor
ON
Starts the motor rotation
OFF
No change to present motor status
ON
Stops the motor rotation
OFF
No change to present motor status
ON
Selects the direction of motor rotation: ON =
FWD. While the motor is rotating, a change of
F/R will start a deceleration, followed by a
change in direction.
OFF
Selects the direction of motor rotation: OFF =
REV. While the motor is rotating, a change of F/
R will start a deceleration, followed by a change
in direction.
ON
Temporarily disables PID loop control. Inverter
output turns OFF as long as PID Enable is active
(A071=01).
OFF
Has no effect on PID loop operation, which
operates normally if PID Enable is active
(A071=01).
L200 Inverter
Description
3–45