Hitachi L200 Series Instruction Manual page 111

Single-phase input 200v class; three-phase input 200v class; three-phase input 400v class
Hide thumbs Also See for L200 Series:
Table of Contents

Advertisement

"B" Function
Func.
Name /
Code
SRW Display
B032 Reactive current setting Calibrate detection of motor's
Io-SET
00100%
B080 [AM] analog signal
gain
AM-Adj
00100%
B082 Start frequency adjust-
ment
fmin
0000.5Hz
B083 Carrier frequency
setting
Carrier
0005.0
B084 Initialization mode
(parameters or trip
history)
INIT Mode
B085 Country code for initial-
ization
INIT Slct
B086 Frequency scaling
conversion factor
Cnv Gain
0001.0
B087 STOP key enable
STP Key
Description
reactive (no load) current for
current monitor, electric
thermal setting, and overload
restriction setting.
Range is 50 to 200%
Adjust of analog output at
terminal [AM],
range is 0 to 255
Sets the starting frequency for
the inverter output, range is 0.5
to 9.9 Hz
Sets the PWM carrier (internal
switching frequency), range is
2.0 to 14.0 kHz
Select the type of initialization
to occur, two option codes:
00... Trip history clear
01... Parameter initialization
TRP
02... Trip history clear and
parameter initialization
Select default parameter values
for country on initialization,
four options, option codes:
USA
00... Japan version
01... Europe version
02... US version
Specify a constant to scale the
displayed frequency for D007
monitor, range is 0.1 to 99.9
Select whether the STOP key
on the keypad is enabled, two
ON
option codes:
00... enabled
01... disabled
L200 Inverter
Defaults
Run
Mode
–FEF
–FU
Edit
(EU)
(USA)
100.
100.
100.
100.
0.5
0.5
5.0
5.0
00
00
01
02
1.0
1.0
00
00
3–39
Units
%
Hz
kHz

Hide quick links:

Advertisement

Table of Contents
loading