Fire-Lite MS-2 Instruction Manual page 34

Fire alarm control panel
Hide thumbs Also See for MS-2:
Table of Contents

Advertisement

Program Options via DIP Switch
Switch Number
SW1
SW2
SW3
synchronization feature as
34
DIP Switch Number
1
Silence Inhibit
2
Auto-silence
3
Temporal Coding
4
Selective Silence (if sync. enabled)
5
Trouble Reminder
6
AC Trouble Delay
7
Autoresettable Supervisory
8
IDC Combination
Waterflow/Supervisory Circuit
1
IDC1 Verification
2
IDC1 Supervisory
3
IDC2 Verification
4
IDC2 Supervisory
5
IDC3 Verification
6
IDC3 Supervisory
7
IDC4 Verification
8
IDC4 Supervisory
1
NAC1 Nonsilenceable
2
NAC1 Disable
3
NAC2 Nonsilenceable
4
NAC2 Disable
No Synchronization
5 & 6
used to select strobe
System Sensor Synchronization
shown to the right
Gentex Synchronization
Wheelock Synchronization
Nonsilenceable Waterflow for
7
Combination Circuit
(only if SW1 switch 8 is ON)
8
spare
Table 3.2 MS-4 DIP Switch Settings
DIP Switch ON
Switch 5
OFF
ON
OFF
ON
MS-2 & MS-4 Series Manual — P/N 51512:G2 10/18/2011
DIP Switch Settings
Switch 6
OFF
OFF
ON
ON