Bryant PREFERRED T6-PRH-A Installation Instructions & Replacement Parts List page 58

Preferred series thermidistat programmable / non-programmable control
Hide thumbs Also See for PREFERRED T6-PRH-A:
Table of Contents

Advertisement

seconds. The control will operate from the temperature sensed by the working
sensor.
E1 - - If the Display Module and the Equipment Control Module cannot
communicate via two- -wire connection, an E1 will be displayed.
E2 - - There is no E2 error message.
E3 - - If Thermidistat Control cannot properly read outdoor temperature, and it is
needed for proper operation, display will indicate "- -- -" in the outdoor
temperature location. If Option 06, 08, 09, 22, 23 or 44 is not set to OFF, display
will indicate "- -- -" in the outdoor temperature location.
E4 - - If Thermidistat Control's internal memory fails, E4 will be displayed.
Replace Thermidistat Control.
E5 - - If Thermidistat Control cannot properly read humidity, E5 will be
displayed. Replace Thermidistat Control. If both Humidify and Dehumidify
have been set to OF, the humidity value will be shown as "- -- -" when viewed
from the humidity menu, but no E5 will be shown in the display.
Table 4 can be used as a troubleshooting tool for determining which outputs will
be active for a particular configuration and each operating mode.
58