Control Circuit

Type
No.
Signal name
Intelligent input common
PLC
Internal 24 VDC
P24
Multi-function Input selection 1
1
Multi-function Input selection 2
2
Multi-function Input selection 3 / safe stop input 1
3/ST1
Multi-function Input selection 4 / safe stop input 2
4/ST2
Multi-function Input selection 5 / PTC thermistor input
5/PTC
Multi-function input selection 6
6
Multi-function input selection 7 / Pulse train input B
7/EB
Multi-function Input selection common (in upper row)
L
Pulse train input A
EA
EO
Pulse train output
Frequency reference power supply
H
Voltage frequency reference signal
O
Current frequency reference signal
OI
Frequency reference common (bottom row)
L
Discrete logic output 1 / EDM output
11/EDM
Discrete logic output 2
12
CMD
GND logic output
Relay commom contact
AL0
AL1
Relay contact, normally open
Relay contact, normally closed
AL2
AM
Analog voltage output
SP
Serial communication terminal
SN

Side by side mounting

Inverter heat loss
Three-phase 200 V class
Model MX2
200 VT
Inverter
200 CT
capacity
240 VT
kVA
240 CT
Rated current (A) VT
Rated current (A) CT
Total heat loss
Efficiency at rated load
Cooling Method
8
Enclosure
A2001
A2002
A2004
0.4
0.6
1.2
0.2
0.5
1.0
0.4
0.7
1.4
0.3
0.6
1.2
1.2
1.9
3.4
1.0
1.6
3.0
12
22
30
89.5
90
93
Self cooling
Function
Source type: connecting [P24] to [1]-[7] turns inputs ON
Sink type: connecting [L] to [1]-[7] turns inputs ON
24 VDC, 30mA
Factory setting: Forward/ Stop
Factory setting: Reverse/ Stop
Factory setting: External trip
Factory setting: Reset
Factory setting: Multi-step speed reference 1
Factory setting: Multi-step speed reference 2
Factory setting: Jog
--
Factory setting: Speed reference
LAD frequency
10 VDC 10 mA max
0 to 10 VDC (10 kΩ)
4 to 20 mA (250 Ω)
--
Factory setting: During Run
Factory setting: Frequency arrival type 1
--
Factory setting: Alarm signal
Under normal operation
AL1 - AL0 Closed
AL2 - AL0 Open
Factory setting: LAD frequency
RS485 Modbus communication
A2007
A2015
A2022
A2037
2.0
3.3
4.1
1.7
2.7
3.8
2.4
3.9
4.9
2.0
3.3
4.5
6.0
9.6
12.0
19.6
5.0
8.0
11.0
17.5
48
79
104
154
94
95
95.5
Forced-air-cooling
Signal level
-
24 VDC, 30 mA
27 VDC max
--
32 kHz max
5 to 24 VDC
10 VDC 2 mA
32 kHz max
27 VDC, 50 mA max
EDM based on
ISO13849-1
R load
250 VAC 2.5 A
30 VDC 3.0 A
I load
250 VAC 0.2 A
30 VDC 0.7 A
0 to 10 VDC 1 mA
A2055
A2075
A2110
6.7
10.3
13.8
19.3
6.0
8.6
11.4
16.2
8.1
12.4
16.6
23.2
7.2
10.3
13.7
19.5
30.0
40.0
56.0
25.0
33.0
47.0
229
313
458
96
96
96
96
Frequency inverters
A2150
23.9
20.7
28.6
24.9
69.0
60.0
625
96

Hide quick links: