Platinum Resistance Thermometer - Omron E5ZE Datasheet

Multipoint temperature controller e5ze series
Hide thumbs Also See for E5ZE:
Table of Contents

Advertisement

Input Ranges
Thermocouple
Input (switch
K (CA)
selectable)
Chromel vs.
(see note 1)
alumel (see
note 2)
Range
C
200 to
1,300
F
300 to
2,300
Setting no.
0
Min. setting unit 1 C or 0.1 C

Platinum Resistance Thermometer

Input (switch
Pt 100
selectable)
(see note 1)
Range
C
100.0 to 500.0
F
100.0 to 900.0
Setting no.
0
Min. setting unit 1 C or 0.1 C
Note: 1. The setting selector set to 0 (K) or 0 (Pt 100) before shipping.
2. A temperature range is factory-set to a range of –200 to 1,300 C (K(CA)) or
3. Thermocouple W is W/Re5-26 (tungsten rhenium 5, tungsten rhenium 26).
J (IC)/L
R/S
Iron vs.
Platinum
constantan
vs. Plati-
constantan
num rhod-
ium 10%
100 to 850 0 to 1,700
100 to
0 to 3,000
1,500
1/8
2/3
4/9
JPt 100
100.0 to 500.0
100.0 to 900.0
1
T (CC)/U
E (CRC)
Copper vs.
Chromel vs.
constantan
rhodium 6%
200 to 400 0 to 600
100 to 1,800 0 to 1,300
300 to 700 0 to 1,100
300 to 3,000 0 to 2,300
5
6
100.0 to 500.0 C (Pt 100).
Multipoint Temperature Controller
B
N
Platinum
Nichrosil
(see note 3)
rhodium
vs. nisil
30% vs.
platinum
0 to 2,300
32 to 4,100
7
A
W
PL-II
(Platinum)
0 to 1,300
0 to 2,300
B
E5ZE
5