Omron E5ZE Datasheet page 11

Multipoint temperature controller e5ze series
Hide thumbs Also See for E5ZE:
Table of Contents

Advertisement

External Connection
Terminal Block Connections
Thermocouple
DC
Thermo-
couple 0
DON'T USE
Thermo-
couple 1
DON'T USE
Thermo-
couple 2
DON'T USE
Thermo-
couple 3
FG
A thermocouple has polarity. Connect thermocouples to the terminal
block correctly using compensating conductor that are suitable for
the thermocouples.
Be sure to use the cold junction compensator (no. 13 and 15) pro-
vided with the E5ZE. The lot and serial numbers of the cold junction
compensator must be identical to those of the E5ZE. Do not touch
the cold junction compensator while operating the E5ZE.
The number of each of the above thermocouples is a point number.
Connecting to Connector Terminal Conversion Unit
Control Output and Memory Bank Designation Input
Current Transformer (CT) Input
DC+
Thermo-
couple 4
DON'T USE
Thermo-
couple 5
DON'T
TOUCH
Thermo-
couple 6
DON'T USE
Thermo-
couple 7
XW2B-20G4 or
XW2B-20G5
Connector Terminal
Memory bank
Conversion Unit
designation input
XW2B-20G4 or
XW2B-20G5
Connector Terminal
Conversion Unit
Platinum Resistance Thermometer
Platinum
resistance
thermometer 0
Platinum
resistance
thermometer 1
Platinum
resistance
thermometer 2
Platinum
resistance
thermometer 3
Make sure there in no difference in resistance among the three con-
ductor of each platinum resistance thermometer used with the E5ZE.
Do not short-circuit terminals 7, 8, 20, and 21.
The number of each of the above platinum resistance thermometer is
a point number.
Control output
Not used
Not used
CT input
Multipoint Temperature Controller
DC+
DC
Platinum
resistance
thermometer 4
Platinum
resistance
thermometer 5
DON'T
DON'T USE
USE
Platinum
resistance
thermometer 6
Platinum
resistance
thermometer 7
FG
Point
number
Point
number
E5ZE
11