Omron CP1L - 12-2007 Operation Manual page 333

Cp1l cpu unit
Table of Contents

Advertisement

Inverter Positioning
Parameter
No.
n153
RS-422A/485 communications
Slave address
n154
RS-422A/485 baud rate selec-
tion
n155
RS-422A/485 parity selection
n156
RS-422A/485 send wait time
n157
RS-422A/485 RTS control
selection
PLC Setup
300
Name
Setting range: 0 to 32
00: Communications disabled
01 to 32: Slave address
0: 2,400 bps
1: 4,800 bps
2: 9,600 bps
3: 19,200 bps
0: Even
1: Odd
2: No parity
Set value: 10 to 65 ms
Setting unit: 1 ms
0: RTS control enabled
1: RTS control disabled
Serial Port Communications Settings
Note
(1) Set the baud rate and parity check settings to the same value as for the
Inverter communications parameters.
(2) Set the serial port to the serial gateway communications mode.
Description
Section 5-3
Default
Setting
0
1
2
2
0
0
10 ms
10 ms
0
0