Pulse Outputs
Operand
P
Port specifier
C
Con-
trol
data
In addition to the various interrupt and high-speed counter functions, INI(880)
can be used to change the pulse output PV or stop the pulse output.
Note
This section explains the functions related to pulse outputs only. For details on
the INI(880) instruction's high-speed counter or interrupt functions, refer to 6-1
Interrupt Functions or 5-1 High-speed Counters .
C
NV
P
NV
First word of new PV
In addition to its interrupt and high-speed counter functions, PRV(881) can be
used to read the pulse output PV or pulse output status information.
The status of the following flags is read as status information:
• Pulse Output Status Flag
• PV Underflow/Overflow Flag
• Pulse Output Amount Set Flag
• Pulse Output Completed Flag
• Pulse Output Flag
• No-origin Flag
• At Origin Flag
• Pulse Output Stopped Error Flag
PRV(881)
P
C
D
0000 hex: Pulse output 0
0001 hex: Pulse output 1
Bits 0 to 3
Not used. (Always 0 hex.)
Not used. (Always 0 hex.)
Pulse output method (See note.)
0000 hex: Pulse output 0
0001 hex: Pulse output 1
1000 hex: PWM output 0
1001 hex: PWM output 1
0002 hex: Change the PV.
0003 hex: Stop pulse output.
NV and NV+1 contain the new PV when changing the
PV. (N contains the rightmost 4 digits and N+1 con-
tains the leftmost 4 digits.)
P: Port specifier
C: Control data
D: First destination word
Section 5-2