The clearances listed below are Minimum distances unless otherwise stated:
A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance
that this fireplace and vent system be installed only in accordance with these instructions.
Caution Requirements
The top, back and sides of the fireplace are defined by
standoffs. The metal ends of the standoff may NOT be
recessed into combustible construction.
Clearance:
A: Mantel Height (min.)
B: Sidewall (on one side)
40-7/8" (1038mm)
C: Ceiling
(room and/or alcove)
D: Mantel Depth (max.)
E: Alcove Width
F: Alcove Depth
G: To Floor
28 - 7/8" (733mm)
Note
D
A
G
NON-COMBUSTIBLE REQUIREMENTS
Wood Stud
HZ54E-11 Gas Fireplace
Fire hazard is an extreme risk if these clearances (air space) to combustible materials
are not adhered to. It is of greatest importance that this fireplace and vent system be
Dimension
Measured From:
20" (508mm)
Top of Fireplace Opening
4" (102mm)
Side of Fireplace Opening
Top of Fireplace Opening
13" (330mm)
30" Above Fireplace Opening
83" (2108mm)
Sidewall to Sidewall (Minimum)
36" (914mm)
Front to Back Wall (Maximum)
Top of Fireplace Opening
0"
No hearth required
F
B
E
Installed Close
to Floor
60-1/2" (1537mm)
Non-combustible
Material
Non-combustible
3-7/8"
( 99mm)
|
2
WARNING
installed only in accordance with these instructions.