Mitsubishi Electric MELSEC QS Series User Manual page 86

Cc-link safety system master module
Hide thumbs Also See for MELSEC QS Series:
Table of Contents

Advertisement

6
PARAMETER SETTING
6
- 6
6.3 Parameter Setting Example
6.3.1 Safety master station network parameter setting
(e) Set a mode of the CC-Link Safety system in "Mode".
Default value: Safety remote net (Ver.1 mode)
Setting range: Safety remote net (Ver.1 mode)
Example) Select "Safety remote net (Ver.1 mode)".
(f) Set transmission speed of the CC-Link Safety system in "Transmission
speed".
Default value: 156kbps
Setting range: 156kbps
Example) Select "2.5Mbps".
(g) Set the monitoring time for a safety remote station in "Safety refresh
monitoring time".
Default value: 200 (ms)
Setting range: 1 to 65535 (ms)
Example) Set to 200ms. (Enter "200".)
(h) Set the monitoring time for a safety remote station in "Safety data
monitoring time".
Default value: 400 (ms)
Setting range: 1 to 65535 (ms)
Example) Set to 400ms. (Enter "200".)
(i) Set a link ID to be allotted for each safety master station in "Link ID".
Default value: 0
Setting range: 0 to 7
Example) Enter "1".
(j) Set the total number of connected stations in the CC-Link safety system
including reserved stations in "All connect count".
Default value : 64
Setting range: 1 to 64
Example) Set to 4 (modules). (Enter "4".)
(k) Specify a refresh device for remote input (RX) in "Remote input (RX)".
Default value : None
Setting range: Device name - Select from X, M, B, D or W.
Example) Enter "X400".
Offline
Hardware test
Line test
625kbps
2.5Mbps
5Mbps
10Mbps
Device number - Within the range of the device
points that the CPU has.