DATA LINK PROCESSING TIME AND STATION
STATUS AT ERROR OCCURRENCE
(2) Safety master station (RY)
5
- 13
5.2 Transmission Delay Time
5.2.2 Safety master station Standard remote I/O station
The following indicates the time from the moment a device of the safety CPU module
turns ON (or OFF) until a standard remote I/O station outputs ON (or OFF).
[Calculation formula]
[Normal value]
(a) Synchronous mode
SM
n + LS + Remote I/O station output response time
• SM:Sequence scan time of safety CPU module
• LS :Link scan time (Refer to Section 5.1.)
• n :(LS/SM) value that is rounded up to the nearest whole number
(Example) When the sequence scan time of the safety CPU module is 20ms,
the link scan time is 3ms, and the remote I/O station response time is
20ms:
SM
= 20
= 43 [ms]
(b) Asynchronous mode
SM + LS + Remote I/O station output response time
• SM:Sequence scan time of safety CPU module
• LS :Link scan time (Refer to Section 5.1.)
(Example) When the sequence scan time of the safety CPU module is 20ms,
the link scan time is 3ms, and the remote I/O station response time is
20ms:
SM + LS + Remote I/O station response time [ms]
= 20 + 3 + 20
= 43 [ms]
Standard remote I/O station (output)
n + LS + Remote I/O station response time [ms]
1 + 3 + 20
*1
[ms]
*1
[ms]