Mitsubishi Electric MELSEC QS Series User Manual page 41

Cc-link safety system master module
Hide thumbs Also See for MELSEC QS Series:
Table of Contents

Advertisement

4
FUNCTIONS
(3) Identifying a safety remote station by module technical version
Whether the module technical version of the model mounted on a safety remote
station matches the one selected for the network parameter or not is determined.
If they do not match, CC-LINK PRODUCT INFO. MISMATCH (Error code 8310) is
saved in the error history of the safety CPU module.
Network parameter setting
Station No.1
Safety remote I/O station
Module technical version "A"
4.2 Detailed Explanation of Functions
4.2.4 Identifying the communication target station (remote I/O station)
Station No.1
Safety remote I/O station
Module technical version "B"
Mismatch in
module technical
versions
1
2
3
4
5
6
7
8
4
- 15