8
PROGRAMMING SPECIFICATIONS
Number
Name
SB004C
Line test acceptance
(5E4
,b12)
status
H
SB004D
Line test complete
(5E4
,b13)
status
H
SB0050
Offline test status
(5E5
,b0)
H
SB0060
Host mode
(5E6
,b0)
H
SB0061
Host type
(5E6
,b1)
H
SB006A
Switch setting status
(5E6
,b10)
H
SB006D
Parameter setting
(5E6
,b13)
status
H
SB006E
Host station operation
(5E6
,b14)
status
H
* 1 Safety remote net (Ver. 1 mode)
* 2 Off line, Hardware test or Line test.
Table8.5 Link Special Relay List (2/3)
Description
Indicates the line test request (SB0008) acceptance status.
OFF : Not accepted
ON
: Instruction acknowledged
Indicates the line test completion status.
OFF : Not executed
ON
: Test complete
Indicates the offline test execution status.
There are the following offline tests: line tests 1 and 2 and
hardware test.
OFF : Not executed
ON
: Being executed
Indicates the setup status of the transmission rate/mode
setting on the host.
OFF : Online
ON
: Other than online
Indicates the station type of the host.
OFF (Fixed) : Master station
Indicates the switch setting status.
OFF : Normal
ON
: Setting error (Error code stored in SW006A)
Indicates the parameter setting status.
OFF : Normal
ON
: Setting error (Error code stored in SW0068)
Indicates the host data link operation status.
OFF : Being executed
ON
: Not executed
8.3 Link Special Relays and Registers (SB/SW)
8.3.1 Link special relays (SB)
Availability
(
:Available,
:Not available)
1
Online*
Offline*
SAFETY
TEST
MODE
MODE
8
- 18
1
2
2
3
4
5
6
7
8

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec-qs0j61bt12

Table of Contents