Unit Status Screen; Effective Occupancy Screen - Daikin Maverick I Installation And Maintenance Manual

Commercial packaged rooftop systems
Hide thumbs Also See for Maverick I:
Table of Contents

Advertisement

Unit Status Screen

The status screen shows basic information about the operation
of the unit, such as mode of operation, inputs, outputs, and
capacity of cooling or heating.
Table 7: Unit Status Screen
Item
Mode
Inputs
Outputs
CAPACITY
Heating: / Cooling:

Effective Occupancy Screen

The Occupancy screen determines whether the unit is
operating in occupied mode, unoccupied mode, or tenant
override. It also displays whether the control is connected to a
network, regular thermostat, or if it is just using its local
sensors for controlling the temperatures.
McQuay OM 1077
Range
STANDBY
Fan Only
COOL STG1 ECON
COOL STG2 CC/ECO
COOL STG1 COMP
COOL STG2 COMP
HEAT STG1 COMP
HEAT STG2 COMP
HEAT STG1 ELEC
HEAT STG2 ELEC
HEAT STG1 GAS
HEAT STG2 GAS
HEAT STG2 CC/ELE
HEAT STG3 CC/ELE
HEAT STG4 CC/ELE
Defrost 1
Defrost 2
24VAC Inputs
Y1 – ON/OFF
Y2 – ON/OFF
W1 – ON/OFF
W2 – ON/OFF
B – ON/OFF
G – ON/OFF
OCC – ON/OFF
LPS1 – ON/OFF
LPS2 – ON/OFF
HPS1 – ON/OFF
HPS2 – ON/OFF
CFS – ON/OFF
SMKS – ON/OFF
FPS – ON/OFF
OUTPUTS
Compressor 1 – ON/OFF
Compressor 2 – ON/OFF
Rev Vlv 1 – ON/OFF
Rev Vlv 2 – ON/OFF
Heat 1 – ON/OFF
Heat 2 – ON/OFF
Outdr Fan 1 – ON/OFF
Outdr Fan 2 – ON/OFF
Indoor Fan – ON/OFF
– 100%
Table 8: Effective Occupancy Screen
Item
Effective Occupancy
Occupied / Unoccupied / TntOverr XXX min
Occupied Mode
Ind Fan Occupcy
Effective Occupancy
Tenant Override, Occupied, or Unoccupied will be displayed
depending on the mode. The DDC Controller allows separate
adjustment of temperature set points and fan operation
according to the building occupancy. This feature is only
available when a thermostat is not controlling the ambient.
For the following sections, Occupied Mode implies that the
calculation for demand utilizes occupied set points, which are
used to satisfy the comfort in the ambient. Unoccupied mode
utilizes unoccupied set points and is normally set to save
energy during periods in which buildings are closed and
unoccupied. Tenant Override Mode is a state in which the
control utilizes occupied set points for a limited amount of
time, after which it returns to unoccupied mode. To start
Tenant Override, the user presses a button on the space sensor
for more than 2 seconds. The Tenant Override period is
adjustable between 2 and 6 hours and it has priority over any
other settings.
All set points are available via network and local human
interface.
Occupied Mode
The Occupied Mode is available through network and user
interface. The possible selections are:
• Off
• Auto
• Cooling only
• Heating only
• Fan Only
• Control by thermostat: not available through network. This
is exclusive to the human interface.
Off mode is the default factory selection, so units do not
accidentally energize during installation. The commissioning
of the rooftop unit therefore requires the configuration of the
Occupied Mode register prior to initial startup.
Auto mode is used with a zone sensor and solid state time
clock.
User Interface
Range
OFF
AUTO
FAN ONLY
HEAT ONLY
COOL ONLY
Ctrl by Tstat
Continuous
Auto
Cont when occup.
17