Control Inputs and Outputs

Control Inputs and Outputs

Control Inputs

Control Inputs
Table 1:
Item
Description
1
ST - Space temperature
2
RAT - Return Air Temperature
3
SAT - Supply Air Temperature
4
OAT - Outside Air Temperature
5
FS1 - Freeze Stat
6
FS2 - Freeze Stat
7
Field Configurable input #1
8
Field Configurable input #2
9
SPA - Set point Adjustment
a
G - Thermostat fan input
10
Y1 - Thermostat 1st stage compressor
11
12
Y2 - Thermostat 2nd stage compressor
13
W1 - Thermostat heating demand
14
W2 - Thermostat heating demand
15
HP1 - High Pressure Switch 1
16
LP1 - Low Pressure Switch 1
HP2 - High Pressure Switch 2
17
18
LP2 - Low Pressure Switch 2
19
Smoke Detector
20
FP - Fan proving
21
CFS - Clogged Filter Switch
22
Occupied input
23
L1 - Comfort Alert 1
24
L2 - Comfort Alert 2
25
Configuration pins
a.Heat Pump Only

Control Input Descriptions

(1) ST - Space temperature.
used to measure the building zone temperature. Sensors should
be located on an interior building wall.
(2) RAT - Return Air Temperature.
return air temperature input. This input is used to monitor
system functionality and to provide diagnostics on how the
system is operating. This sensor input can be used in place of
the space temperature input. It also acts as a backup in case of
a space temperature sensor failure.
(3) SAT - Supply Air Temperature.
supply air temperature input. This input is used to monitor
system functionality and to provide diagnostics on how the
system is operating.
(4) OAT - Outside Air Temperature.
temperature sensor is factory installed in the unit to monitor
the outside temperature. This temperature is used to control the
economizer.
(5) FS1 - Freeze Stat.
When the thermistor reads a
temperature below 37°F continuously for 15 minutes, the
6
Thermistor 10k?
Thermistor 10k?
Thermistor 10k?
Thermistor 10k?
Thermistor 10k?
Thermistor 10k?
Thermistor 10k?
Analog input
Resistance input
24VAC
24VAC
24VAC
24VAC
24VAC
24VAC
24VAC
24VAC
24VAC
24VAC
24VAC
24VAC
24VAC
Pulsed 24VDC
Pulsed 24VDC
Polarized Plug P11
The space temperature sensor is
The DDC Controller has a
The DDC Controller has a
The outdoor air
Type
Field Installed (optional)
Factory Installed
Factory Installed
Factory Installed
Factory Installed
Factory Installed
Field Installed (optional)
Field Installed (optional)
Field Installed (optional)
Field Installed (optional)
Field Installed (optional)
Field Installed (optional)
Field Installed (optional)
Field Installed (optional)
Factory Installed
Factory Installed
Factory Installed
Factory Installed
Factory or Field Installed
Factory Installed
Factory Installed
Field Installed (optional)
Factory or Field Installed (optional)
Factory or Field Installed (optional)
Factory Installed
control will shutdown compressor #1 and continue to run the
indoor blower. The system will return to normal operation
when the thermistor reads a temperature above 42°F for 15
minutes.
(6) FS2 - Freeze Stat.
temperature below 37°F continuously for 15 minutes, the
control will shutdown compressor #2 and continue to run the
indoor blower. The system will return to normal operation
when the thermistor reads a temperature above 42°F for 15
minutes.
(7) Field Configurable input #1.
of a 10K ohm temperature sensor (e.g. discharge air
temperature sensor installed in supply duct).
(8) Field Configurable input #2.
of an analog input (e.g. 0-10VDC input from outdoor airflow
monitoring station).
(9) SPA - Set point Adjustment.
enabled, then the control will consider the hard wired
potentiometer input to determine occupied set points only. If
the remote set point adjustment is enabled but the input reads
Option
When the thermistor reads a
Used for custom installation
Used for custom installation
If the set point adjustment is
McQuay OM 1077