Daikin Maverick I Installation And Maintenance Manual page 48

Commercial packaged rooftop systems
Hide thumbs Also See for Maverick I:
Table of Contents

Advertisement

Maintenance
Figure 40: System Charging Chart: MPS 025B
48
SYSTEM CHARGE CHAR
25 TON, CIRCUITS 1 & 2
CAUTION:
BOTH COMPRESSORS MUST BE OPERATING BEFORE CHECKING
REFRIGERANT CHARGE.
RETURN AIR TEMPERATURE MUST BE WITHIN COMFORT CONDITIONS
BEFORE FINAL REFRIGERANT CHECK!
MEASURE PRESSURE AT COMPRESSOR SUCTION AND DISCHARGE.
INSTRUCTIONS:
MEASURE OUTDOOR AMBIENT TO UNIT.
PLACE (X) ON CHART WHERE SUCTION AND DISCHARGE INTERSECT.
IF (X) IS BELOW OUTDOOR AMBIENT LINE, ADD CHARGE AND REPEAT
STEPS 1-3.
IF (X) IS ABOVE OUTDOOR AMBIENT LINE, RECOVER EXCESS CHARGE
AND REPEAT STEPS 1-3.
575
550
525
500
475
450
425
400
375
350
325
300
275
250
225
100
105
110
115
575
550
525
500
475
450
425
400
375
350
325
300
275
250
225
100
105
110
115
120
SUCTION PRESSURE (PSIG)
T - REFRIGERANT
410A
120
125
130
135
140
145
150
SUCTION PRESSURE (PSIG)
25 TON, CIRCUIT
1
125
130
135
140
145
150
25 TON, CIRCUIT
2
115
105
95
85
75
65
55
155
160
165
115
105
95
85
75
65
55
155
160
165
Daikin IM 972-1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Maverick mps015bMaverick mps025b

Table of Contents