Figure 39: System Charging Chart: MPS 020B
Daikin IM 972-1
SYSTEM CHARGE CHAR
20 TON, CIRCUITS 1 & 2
CAUTION:
BOTH COMPRESSORS MUST BE OPERATING BEFORE CHECKING
REFRIGERANT CHARGE.
RETURN AIR TEMPERATURE MUST BE WITHIN COMFORT CONDITIONS
BEFORE FINAL REFRIGERANT CHECK!
MEASURE PRESSURE AT COMPRESSOR SUCTION AND DISCHARGE.
INSTRUCTIONS:
MEASURE OUTDOOR AMBIENT TO UNIT.
PLACE (X) ON CHART WHERE SUCTION AND DISCHARGE INTERSECT.
IF (X) IS BELOW OUTDOOR AMBIENT LINE, ADD CHARGE AND REPEAT
STEPS 1-3.
IF (X) IS ABOVE OUTDOOR AMBIENT LINE, RECOVER EXCESS CHARGE
AND REPEAT STEPS 1-3.