Outside Slab Installation; Attaching Exhaust And Combustion Air Inlet Hoods; Horizontal Conversion Procedure - Daikin Maverick I Installation And Maintenance Manual

Commercial packaged rooftop systems
Hide thumbs Also See for Maverick I:
Table of Contents

Advertisement

Outside Slab Installation

These units are designed certified for outdoor installation
only. Installation inside any part of a structure can result in
inadequate unit performance as well as property damage.
Installation inside can also cause recirculation of flue
products into the conditioned space resulting in personal
injury or death.
Typical outdoor slab installation is shown in
1
Select a location where external water drainage cannot
collect around unit.
2
Provide a level slab sufficiently high enough above grade
to prevent surface water from entering the unit
3
Locate the unit to provide proper access for inspection
and servicing as shown in
4
Locate unit where operating sounds will not disturb
owner or neighbors.
5
Locate unit so roof runoff water does not pour directly on
the unit. Provide gutter or other shielding at roof
level.Do not locate unit in an area where excessive snow
drifting may occur or accumulate.
6
Where snowfall is anticipated, the height of the unit
above the ground level must be considered. Mount unit
high enough to be above anticipated maximum area
snowfall and to allow combustion air to enter the
combustion air inlet.
7
Select an area which will keep the areas of the vent, air
intake, and A/C condenser fins free and clear of
obstructions such as weeds, shrubs, vines, snow, etc.
Inform the user accordingly.
Figure 1: Outside Slab Construction
Daikin IM 972-1
DANGER
Figure
1.
Figure 3, page
6.
Mechanical Installation
Attaching Exhaust and Combustion Air Inlet
Hoods
IMPORTANT: Do not operate this unit without the exhaust/
combustion air inlet hood properly installed. The hood ships in
a carton in the blower compartment inside the unit and must be
attached when the unit is installed. See
To attach exhaust/combustion air inlet hood:
1
Remove screws securing blower access panel and
remove access panel. For location of blower access
panel, see
Figure 3, page
2
Remove exhaust/combustion air inlet hood from the
carton, located inside the blower compartment.
3
Attach blower access panel.
4
Attach the combustion air inlet/exhaust hood with
screws. Reference
Figure 4, page 6
Screws are in carton with the hood.
5
Vent the unit using the flue exhaust hood, as supplied
from the factory, without alteration or addition. The only
exception is with factory approved additions.

Horizontal Conversion Procedure

Downflow To Horizontal
1
Remove the screws and covers from the outside of the
supply and return sections. Also remove and discard the
cover plate.
2
Install the covers over the bottom supply and return
openings, painted side up, inserting the leading flange
under the bracket provided. Place the back flange to top
of the front bracket provided. See
page
7.
3
Secure the return and supply cover to front bracket with
two (2) screws.
Figure 2: Horizontal Conversion Detail
Figure 4, page
6.
6.
for proper location.
Figure 2
and
Figure 6,
5