Mca And Mcop - Daikin Maverick I Installation And Maintenance Manual

Commercial packaged rooftop systems
Hide thumbs Also See for Maverick I:
Table of Contents

Advertisement

Table 13: Compressor and Condenser Motor Data – 575 Volt
Data
Compressor Motor
No.
Phase
RPM
HP, Compressor 1
Amps (RLA), Comp. 1
Amps (LRA), Comp. 1
HP, Compressor 2
Amps (RLA), Comp. 2
Amps (LRA), Comp. 2
Condenser Motor
No.
Phase
HP
Amps (FLA, each)
Amps (LRA, each)
Note:
*Unit operating voltage range is 518 - 632

MCA and MCOP

Table 14: Unit MCA and MCOP Data
MPS Model
Low Static
Fan Drive
MCA
78.0
015
MCOP
100.0
MCA
101.0
020
MCOP
125.0
MCA
147.0
025
MCOP
175.0
Daikin IM 972-1
Electrical Data (575 V)*
MPS
MPS
MPS
015B
020B
025B
2
3
3450
7-1/2
10
11-1/2
9.0
12.8
14.7
78
80
100
7-1/2
7-1/2
11-1/2
9.0
12.2
14.7
78
80
100
4
6
1
1/3
0.5
1.5
208/230
High Static
Fan Drive
81.0
100.0
109.0
125.0
149.0
175.0
Voltage
460
Low Static
High Static
Fan Drive
Fan Drive
38.0
40.0
45.0
50.0
52.0
56.0
60.0
70.0
60.0
63.0
70.0
80.0
Electrical Data
575
Low Static
High Static
Fan Drive
Fan Drive
28.0
30.0
35.0
35.0
40.0
42.0
50.0
50.0
47.0
50.0
60.0
60.0
25

Hide quick links: