Optional Gas Heat; Gas Piping; Electric Heat Application Data; Gas Heat Application Data - York 20 Series Installation Manual

Gas/electric single package air conditioners
Table of Contents

Advertisement

349215-JIM-B-1008
TABLE 3: ELECTRIC HEAT APPLICATION DATA
NOMINAL
HEATER SIZE
(KW)
18
36
54
72

OPTIONAL GAS HEAT

These gas-fired heaters have aluminized-steel or
optional stainless steel, tubular heat exchangers with
spark ignition with proven pilot.
TABLE 4: GAS HEAT APPLICATION DATA
0 To
2,000 To
2,000 Feet
4,500 Feet
Above
Sea Level
Sea Level
Max.
Min.
Max.
300
150
270
400
200
360
1.
On VAV units, individual VAV boxes must be full open in heating mode to insure airflow falls within
temperature rise range.

GAS PIPING

Proper sizing of gas piping depends on the cubic feet
per hour of gas flow required, specific gravity of the gas
and the length of run. "National Fuel Gas Code" Z223.1
(in U.S.A.) or the current Gas Installation Codes CSA-
B149.1 (in Canada) should be followed in all cases
unless superseded by local codes or gas utility require-
ments. Refer to the Pipe Sizing Table 5.
The heating value of the gas may differ with locality.
The value should be checked with the local gas utility.
There may be a local gas utility requirement
NOTE:
specifying a minimum diameter for gas piping.
All units require a one-inch pipe connection at
the entrance fitting.
14
VOLTAGE
3-PHASE,
15 TON
60 HZ
208/230,460,575
208/230,460,575
208/230
460,575
208/230
460,575
Output Capacity (Mbh)
0 To
2,000 Feet
Above
Above
Sea Level
Min.
Max.
135
240
180
320
MINIMUM CFM UNIT SIZE
17.5 TON
4500
4500
5000
6000
4500
5000
4500
All gas heaters are shipped from the factory equipped
for natural gas use, but can be field converted to L.P./
Propane with Kit Model # 1NP0418. See Gas Heat
Application Data Table.
2,000 To
4,500 Feet
Available
Above
on Models
Sea Level
Max.
213
15, 17.5, 20 & 25 Ton
281
15, 17.5, 20 & 25 Ton
TABLE 5: PIPE SIZING
Length in Feet
10
20
30
40
50
60
70
80
90
100
Maximum capacity of pipe in cubic feet of gas per hour. (Based upon
a pressure drop of 0.3 inch water column and 0.6 specific gravity
gas).
20 TON
25 TON
6000
7500
Temp.
Rise ºF
Gas
At
Rate
(Ft./Hr.)
Full Input
Min.
279
20
372
30
Nominal Iron Pipe Size
1 in.
1-1/4 in.
520
1,050
350
730
285
590
245
500
215
440
195
400
180
370
170
350
160
320
150
305