Optional Electric Heat; Optional Gas Heat; Electric Heat Minimum Supply Air; Side Entry Gas Piping - York ZV-06 Installation Manual

Table of Contents

Advertisement

Optional electric heat

The factory-installed heaters are wired for single point power
supply. You only need to bring the power supply into the single
point terminal block.
Table 14: Electric heat minimum supply air
Size (tons)
-06
(6.5)
-07
(7.5)
-08
(8.5)
-10
(10)
-12
(12.5)

Optional gas heat

The optional gas-fired heaters have aluminized-steel or optional
stainless steel, tubular heat exchangers with spark ignition.
Gas piping
Proper sizing of gas piping depends on the cubic feet per hour
of gas flow required, specific gravity of the gas, and the length
of run.
Follow the "National Fuel Gas Code" Z223.1 (in U.S.A.) or the
current Gas Installation Codes CSA-B149.1 (in Canada) in all
cases unless they are superseded by local codes or gas utility
requirements.
See Table 15, Gas pipe sizing - capacity of pipe, on page 36.
The heating value of the gas may vary by locality. You must
check the value with the local gas utility.
Johnson Controls Ducted Systems
Model
Voltage
208/230-3-60
ZV
460-3-60
208/230-3-60
ZV
460-3-60
208/230-3-60
ZV
460-3-60
208/230-3-60
ZV
460-3-60
208/230-3-60
ZV
460-3-60
These CSA approved heaters are located within the central
compartment of the unit with the heater elements extending in
to the supply air chamber.
Fuses are supplied, where required, by the factory. Some kW
sizes require fuses and others do not. See Table 14 for
minimum CFM limitations.See Table 12 for electrical data.
Minimum supply air (CFM)
Heater kW
9
18
1950
1950
1950
1950
1950
1950
1950
1950
1950
2250
2250
2250
2550
2550
2550
2550
2550
2550
-
3000
3000
-
3000
3000
-
3750
3750
-
3750
3750
Figure 22: Side entry gas piping
5567611-BIM-B-1218
24
36
54
1950
-
1950
-
1950
-
2250
-
2550
-
2550
-
3000
3500
3000
3000
3750
4000
3750
3750
OPTIONAL
COIL
GUARD
SHOWN
35

Advertisement

Table of Contents
loading

This manual is also suitable for:

Zv seriesZv-07Zv-08Zv-10Zv-12

Table of Contents