OPTIONAL HOT GAS BYPASS (HGBP)

To allow for low cooling load operation, a direct-acting,
pressure-modulating bypass control valve installed on
the system #1 discharge line is used to divert high tem-
perature, high pressure refrigerant around the TXV in
FIGURE 9 - ENTHALPY SETPOINT ADJUSTMENT
Johnson Controls Unitary Products
order to maintain a desired minimum evaporator pres-
sure.
The opening pressure of the bypass valve is fully
adjustable between 0 and 80 psig with a factory-setting
of 60 psig. HGBP is standard on all units with VAV and
optional with CV units.