UNIT CONTROL BOARD FLASH CODES

Various flash codes are utilized by the unit control
board (UCB) to aid in troubleshooting. Flash codes are
distinguished by the short on and off cycle used
(approximately 200ms on and 200ms off). To show
normal operation, the control board flashes a 1 second
on, 1 second off "heartbeat" during normal operation.
This is to verify that the UCB is functioning correctly.
Do not confuse this with an error flash code. To prevent
confusion, a 1-flash, flash code is not used.
Alarm condition codes are flashed on the UCB lower
left Red LED, See Figure 28. While the alarm code is
being flashed, it will also be shown by the other LEDs:
lit continuously while the alarm is being flashed. The
total of the continuously lit LEDs equates to the number
TABLE 27: UNIT CONTROL BOARD FLASH CODES
FLASH CODE
On Steady
This is a Control Failure
1 Flash
Not Applicable
2 Flashes
Control waiting ASCD
3 Flashes
HPS1 Compressor Lockout
4 Flashes
HPS2 Compressor Lockout
5 Flashes
LPS1 Compressor Lockout
6 Flashes
LPS2 Compressor Lockout
7 Flashes
FS1 Compressor Lockout
8 Flashes
FS2 Compressor Lockout
9 Flashes
Ignition Control Locked Out / Ignition Control Failure
10 Flashes
Compressors Locked Out on Low Outdoor Air Temperature
Compressors locked out because the Economizer is using free
11 Flashes
1
Cooling
12 Flashes
Unit Locked Out due to Fan Overload Switch Failure
13 Flashes
Compressor Held Off due to Low Voltage
14 Flashes
EEPROM Storage Failure
OFF
No Power or Control Failure
1.
Non-alarm condition.
64
DESCRIPTION
1
1
of flashes, and is shown in the table. Pressing and
releasing the LAST ERROR button on the UCB can
check the alarm history. The UCB will cycle through the
last five (5) alarms, most recent to oldest, separating
each alarm flash code by approximately 2 seconds. In
all cases, a flashing Green LED will be used to indicate
non-alarm condition.
In some cases, it may be necessary to "zero" the
ASCD for the compressors in order to perform trouble-
shooting. To reset all ASCDs for one cycle, press and
release the UCB TEST/ RESET button once.
Flash codes that do and do not represent alarms are
listed in Table 27.
GREEN
RED
LED
LED
16
-
-
Flashing
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
Off
On
1
Flashing
On
Flashing
On
Off
On
Flashing
On
Off
On
Off
Off
Johnson Controls Unitary Products
RED
RED
LED
LED
8
4
2
-
-
-
-
-
-
Off
On
Off
On
On
Off
On
Off
On
On
On
On
Off
Off
Off
Off
Off
On
Off
On
On
Off
On
Off
On
On
Off
Off
RED
LED
1
-
-
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
Off

Advertisement

Table of Contents
loading

This manual is also suitable for:

J15djJ18djJ20djJ25dj

Table of Contents