Adjustments and service procedures

5.5.1

Battery care

Before handling batteries, read the
!
relevant safety precautions and act
accordingly.
If the battery is still dry, it must be activated as
described in section "Activating a dry-charged
battery".
The battery must be in operation within 2 months
from being activated; if not, it needs to be recharged
first.
5.5.1.1
Electrolyte
!
Read
the
safety
carefully.
Electrolyte in batteries is a sulphuric acid solution in
distilled water.
The solution must be made up before being
introduced into the battery.
5.5.1.2
Activating a dry-charged battery
– Take out the battery.
– Battery and electrolyte must be at equal
temperature above 10°C.
– Remove cover and/or plug from each cell.
– Fill each cell with electrolyte until the level
reaches 10 to 15 mm above the plates, or to the
level marked on the battery.
– Rock the battery a few times so that possible air
bubbles can escape; wait 10 minutes and check the
level in each cell once more; if required, add
electrolyte.
– Refit plugs and/or cover.
– Place the battery in the generator.
5.5.1.3
Recharging a battery
Before and after charging a battery, always check the
electrolyte level in each cell; if required, top up with
distilled water only. When charging batteries, each
cell must be open, i.e. plugs and/or cover removed.
Use a commercial automatic battery
!
instructions
charger
manufacturer's instructions.
Apply with preference the slow charging method and
adjust the charge current according to the following
rule of thumb: battery capacity in Ah divided by 20
gives safe charging current in Amp.
5.5.1.4
Make-up distilled water
The amount of water evaporating from batteries is
largely dependant on the operating conditions, i.e.
temperatures, number of starts, running time between
start and stop, etc...
If a battery starts to need excessive make-up water,
this points to overcharging. Most common causes are
high temperatures or a too high voltage regulator
setting.
according
to
its
- 53 -
If a battery does not need any make-up water at all
over
a
considerable
time
of
undercharged battery condition may be caused by
poor cable connections or a too low voltage regulator
setting.
5.5.1.5
Periodic battery service
– Keep the battery clean and dry.
– Keep the electrolyte level at 10 to 15 mm above
the plates or at the indicated level; top up with
distilled water only. Never overfill, as this will
cause poor performance and excessive corrosion.
– Record the quantity of distilled water added.
– Keep the terminals and clamps tight, clean, and
lightly covered with petroleum jelly.
– Carry out periodic condition tests. Test intervals
of 1 to 3 months, depending on climate and
operating conditions, are recommended.
– If doubtful conditions are noticed or malfunctions
arise, keep in mind that the cause may be in the
electrical system, e.g. loose terminals, voltage
regulator maladjusted, poor performance of
generator, etc...