Q1 ....... Main circuit breaker
Interrupts the power supply to X1 when a
short-circuit occurs at the load side, or when
the earth leak detector (30 mA) or the
overcurrent
protection
is activated or when the shunt
QAS 20: 32 A)
trip is energized. It must be reset manually
after eliminating the problem.
X1 ....... Main power supply (400 V AC)
Terminals L1, L2, L3, N (= neutral) and PE
(= earthing), hidden behind the control panel
door and behind a small transparent door.
N13 ..... Earth leak detector
Detects and indicates an earth fault current
and activates the main circuit breaker Q1.
The detection level can be set at 0.03 A fixed
with instantaneous trip but can also be
adjusted between 0.1 A and 1 A with time
delayed (0 - 0.5 sec) trip. N13 has to be reset
manually after eliminating the problem
(reset button marked R). It can be overridden
by means of the earth leak switch (S13,
labelled IΔN) but has to be tested monthly
(by pushing test button T).
S13 ..... Lock-out switch for earth fault
protection (N13)
This switch is located inside the cubicle and
is labelled IΔN.
(QAS 14:
20 A,
Position O: No tripping of the main circuit
breaker Q1 when an earth fault occurs.
Position 1: Tripping of the main circuit
breaker Q1 when an earth fault occurs.
Position O will only be used in
!
conjunction with an external earth
fault protection unit (e.g. integrated
in a distribution board).
If S13 is in position O, proper
earthing is of the utmost importance
for
Eliminating
protection can lead to serious injury
or even death for anybody touching
the unit or the load.
2.4.3

Electronic speed regulator

The electronic speed regulator makes sure that the
output frequency of the generator is fixed,
independent of the amount of load.
the
safety
of
the
user.
any
earth
fault
- 20 -