Gas Pressure - Riello RS 45/E LN Installation, Use And Maintenance Instructions

Forced draught gas burner
Table of Contents

Advertisement

Make sure that the gas train is properly installed by
checking for any fuel leaks.
The operator must use appropriate tools for instal-
lation.
See the accompanying instructions for the adjust-
ment of the gas train.
WARNING
4.8.4

Gas pressure

The Tab. J is used to calculate manifold pressure taking into ac-
count combustion chamber pressure.
Gas manifold pressure measured at test point 1)(Fig. 19), with:
combustion chamber at 0" WC;
burner operating at maximum output;
column 1: gas ring R2-R3)(Fig. 13) adjusted as indicated in di-
agram (Fig. 14);
column 2: pressure loss at gas butterfly valve 8)(Fig. 18) with
maximum opening: 90°.
Calculate the approximate maximum output of the burner as fol-
lows:
 subtract the combustion chamber pressure from the gas pres-
sure measured at test point 1)(Fig. 19);
 find the nearest pressure value to your result in column 2 for
the burner in question;
 read off the corresponding output on the left.
Example with natural gas G20
Maximum output operation
Gas ring 2-5)(Fig. 13) adjusted as indicated in diagram
(Fig. 14)
Gas pressure at test point 1)(Fig. 19)
Pressure in combustion chamber
3.69 - 0.79
A maximum output of 1136 MBtu/hr shown in Tab. J corresponds
to 2.90" WC pressure, column 1.
This value serves as a rough guide, the effective delivery must be
measured at the gas meter.
The data of thermal output and combustion
head gas pressure are related to full open (90°)
gas butterfly valve.
WARNING
20026767
Installation
MBtu/hr
= 3.69" WC
= 0.79" WC
= 2.90" WC
20
GB
kW
720
211
949
278
1136
333
1327
389
1515
444
1706
500
1894
555
2085
611
p ("WC)
1
2
1.38
0.12
2.16
0.15
2.90
0.19
3.66
0.23
4.21
0.27
4.72
0.31
5.12
0.35
5.31
0.39
Tab. J
D2786
Fig. 19

Advertisement

Table of Contents
loading

This manual is also suitable for:

C9341400

Table of Contents